REFNET Pipe System EDUS39-606A-N
4 Installation of Outdoor Units
2.2 Field Refrigerant Piping
1. The following materials should be used for all refrigerant piping.
Materials: Deoxidized phosphorous seamless copper pipe or equivalent
2. The tips for insulation
Both Gas, Liquid piping must be insulated.
Materials: Glass fiber or heat-resistant polyethylene foam.
Thickness: 1/2 inch (12.7 mm) or more
Heat resistance: Gas pipe : 250°F or more / Liquid pipe : 160°F or more
Insulation of single pipe only Insulation of both liquid and gas pipe
2.3 REFNET Joints and Headers
2.3.1 REFNET Joints
For gas and liquid branch pipes
Make sure that all branch pipes are fitted such that they branch either horizontally or vertically.
When the size of the selected field piping is different from that of branch pipe then the connecting section should be
cut with a pipe cutter as shown in the following figure.