Daikin RXYMQ36MVJU Instruction Manual Page 24

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 23
Installation EDUS39-606A-N
23 Installation of Outdoor Units
CAUTION
Do not operate the air conditioner until the refrigerant pip-
ing work is completed.
Operating the air conditioner before the refrigerant piping
work is completed may damage the compressor.
Install a ground leakage circuit breaker.
The inverter is provided in the air conditioner. In order to
prevent malfunction of the a ground leakage circuit breaker
itself, use a breaker resistant to higher harmonics.
Electricians having sufficient knowledge should perform
the electrical wiring work.
All wiring must comply with local electrical codes and
National Electrical Code (NEC).
Perform the electric wiring work in accordance with the
ELECTRIC WIRING DIAGRAM label.
Make sure to turn OFF the branch switch and overcurrent
breaker before starting the work.
Perform grounding to the indoor units and outdoor units.
Use only copper wires.
Make sure to turn the power off before starting the electric
wiring work.
Do not turn ON any switch until the work is completed.
The outdoor unit has an inverter which generates noise
and charges the outer casing with the leakage current. The
outdoor unit should be grounded so that the effect of the
generated noise on other equipment can be reduced, and
the outer casing can be discharged.
As this unit is equipped with an inverter, installing a phase
advancing capacitor will not only reduce the power factor
improvement factor, but may also cause the capacitor to
overheat due to high-frequency waves. Therefore, never
install a phase-advancing capacitor.
Never push excessive electric wires into the units.
Protect electric wires with conduit tubes or vinyl tubes so
that they will not be damaged by edges of knockout holes.
Fix electric wires with clamps as accessories so that they
will not come into contact with pipes and stop valves.
Refer to Section Power supply wiring connection proce-
dure.
Connection example of whole system wiring
Routing power supply wiring and transmission
wiring
Let the power supply wiring with a conduit pass through one of
the knockout holes on the front or side cover, and let the trans
-
mission wiring with a conduit pass through another knockout
hole.
For protection from un-insulated live parts, thread the
transmission wiring through the included insulating tube
and secure it with the included clamp.
Insulating tube
(accessory)
Clamp
(accessory)
Transmission
wiring
(3in.)
Precautions when knocking out knock holes:
To punch the knockout hole, hit it with a hammer.
After removing the knockout, paint the edges to prevent rust-
ing.
Use conduit for both the power supply wiring and transmis-
sion wiring.
Outside the unit, make sure to keep the wirings five inches
away or the outdoor unit may be affected by external elec-
trical noise and malfunction or fail.
Be sure to connect the power supply wiring to the terminal
block and secure it as described in Section Power supply
wiring connection procedure.
Fix the wiring between the units in accordance with Section
Transmission wiring connection procedure.
To prevent wires from touching the piping, secure them
with the accessory clamps.
Make sure the wirings will not be pinched by the front
panel, and close the panel firmly.
Route the conduit along the unit by using a elbow socket to
prevent it from being stepped on.
Power
Remote
controller
Indoor
unit
Ground
Power
Ground
Outdoor unit
16V
208-230V
208-230V
16V 16V 16V
Earth leakage
circuit breaker
Overcurrent
breaker (fuse)
Branch switch
Page view 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 30 31

Comments to this Manuals

No comments