Daikin ATX20JV1B Specifications Page 30

  • Download
  • Add to my manuals
  • Print
  • Page
    / 156
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 29
Main Functions SiBE041010
20 Function and Control
1.6 Thermostat Control
Thermostat control is based on the difference between the room temperature and the target
temperature.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Heating
B
A
OFF
ON
C
Cooling : –0.5˚C
Dry : –0.5˚C
Room temperature – target temperature
–1.5˚C
Cooling : –2.0˚C
Dry : –2.5 ~ –2.0˚C
(R11658)
B
A
OFF
ON
C
1.5˚C
1.0˚C
Room temperature – target temperature
0˚C
(R11895)
Page view 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 155 156

Comments to this Manuals

No comments