Troubleshooting SiBE041010
66 Service Diagnosis
4.8 Outdoor Unit PCB Abnormality
Remote
Controller
Display
E1
Method of
Malfunction
Detection
The system follows the microprocessor program as specified.
The system checks to see if the zero-cross signal comes in properly.
Malfunction
Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Broken harness between PCBs
Noise
Momentary fall of voltage
Momentary power failure, etc
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
YES
(R12024)
YES
NO
NO
Replace the outdoor unit
PCB (2).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (1).
Replace the harness.
Check to see if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
Is the harness
broken?
Turn on the power again.
Set the fan operation by
remote controller, and cancel
the standby electricity saving
function before you check the
LED A.
Wait at least for 7 sec. after
turning on the power.