Daikin ATX20JV1B Specifications Page 95

  • Download
  • Add to my manuals
  • Print
  • Page
    / 156
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 94
SiBE041010 Troubleshooting
Service Diagnosis 85
4.22 Output Overcurrent Detection
Remote
Controller
Display
L5
Method of
Malfunction
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats 8 times, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal supply voltage
Defective outdoor unit PCB
Defective compressor
Page view 94
1 2 ... 90 91 92 93 94 95 96 97 98 99 100 ... 155 156

Comments to this Manuals

No comments