SiBE041010 Indoor Unit
Removal Procedure 115
1.7 Removal of Indoor Heat Exchanger
Procedure Warning Be sure to wait 10 minutes or more after turning off all power
supplies before disassembling work.
Step Procedure Points
1. Disconnect the refrigerant
piping.
Preparation
Remove the electrical box
according to the “Removal
of Electrical Box”.
Caution
For pump down operation, be
sure to stop the compressor
before disconnecting the
refrigerant pipe. If the
refrigerant pipe is
disconnected with the
compressor running and the
stop valve opened, air may be
sucked in to generate an
over-pressure in refrigeration
cycle, thus resulting in pipe
rupture or accidental injury.
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
1
Remove the screws
which fix the indoor
heat exchanger to the
installation plate.
2
Lift the indoor unit with
a wooden base.
3
Place a plastic sheet
under the drain pan as
remaining drain may
leak.
4
Disconnect the flare nut
for gas piping with 2
wrenches.
Caution
From the viewpoint of global
environment protection,
make sure to use a vacuum
pump for air purging.
(R8014)
(R8015)
Wooden base
Drain hose
Extension drain hose
Connecting wires
(R8016)
(R8017)