Daikin ATX20JV1B Specifications Page 102

  • Download
  • Add to my manuals
  • Print
  • Page
    / 156
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 101
Check SiBE041010
92 Service Diagnosis
5.1.3 Thermistor Resistance Check
Check No.06 Disconnect the connectors of the thermistors from the PCB, and measure the resistance of
each thermistor using tester.
The relationship between normal temperature and resistance is shown in the table and the
graph below.
For the models in which the thermistor is directly mounted on the PCB, disconnect the
connector for the PCB and measure.
Thermistor Room temperature thermistor Other thermistors
R25°C = 10 k R25°C = 20 k
Temperature (°C) B = 3435 B = 3950
–20 73.4 (k) 211.0 (k)
–15 57.0 150.0
–10 44.7 116.5
–5 35.3 88.0
0 28.2 67.2
5 22.6 51.9
10 18.3 40.0
15 14.8 31.8
20 12.1 25.0
25 10.0 20.0
30 8.2 16.0
35 6.9 13.0
40 5.8 10.6
45 4.9 8.7
50 4.1 7.2
(11952)
Other thermistorsRoom temperature thermistor
(˚C)(˚C)
50
25
0
–15
0
15 30
45
(k)
(k)
–15
0
15 30
45
150
100
50
Tester
Resistance range
RTH1
Tester
(R3460)
Page view 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 155 156

Comments to this Manuals