SiE25-110 Function Details
Function and Operation 79
Using Conditions
for Remote
Controller
Thermostat
(Applicable models: FHY-B, FHYC-K, FUY-F, FAY-FA only)
Remote controller thermostat is equipped only in wired remote controller.
Even when “ use remote controller thermostat ” is selected in service mode, the remote
controller thermostat may not be used.
< Conditions not to use >
1. When the remote controller thermostat malfunctions.
2. When the one remote controller group control is applied.
( Excluding simultaneous ON/OFF operation )
3. When conditions relating set temperature with remote controller and suction air temperature
are out of the operating zone of remote controller thermostat shown in below diagram.
( Excluding when automatic operation mode is selected. Whenever operation is in the
automatic mode, remote controller thermostat can be used. )