SiE25-110 Function Details
Function and Operation 91
4.2.21 Protection Control by Overall Current
Monitors the overall current and restricts the upper limit compressor operating frequency to
prevent circuit breakers from exceeding the rated capacity.
Upper limit current (A)
Takes the following values depending on the outside temperature.
Also varies depending on model.
ABCD
RZP71DV1, DVAL 16.5A 16.5A 17.2A 6.3A
RZP100DV1, DVAL 21.0A 18.0A
21.2A 16.3A
RZP125DV1 23.6A 23.6A
RZP125DTAL 23.8A 13.1A
14.5A 7.5A
RZP140DTAL 24.5A 17.2A
OR
Normal operation
Outdoor unit current upper limit
current value
Upper limit compressor operating
frequency = Maximum frequency
Outdoor unit current upper
limit current value
Outdoor unit current
>upper limit current value
Upper limit compressor operating frequency
–1 step/10 sec
Upper limit compressor operating frequency
+1 step/3 min
Outdoor unit current>upper
limit current value
(S2563)
Overall current
Current A
Current C
Current B
Current D
(S2564)