SiE25-110 RZP71~140D
Removal Procedure 217
3. Removing the active
module (for single-phase
unit only)
Warning
Caution for Electric Shocks
1. Turn the power supply off
without fail before servicing.
2. Do not touch the charging
area (high voltage) for 10
minutes after turning the
power supply off.
3. If you must touch the
charging area, be sure that
the main circuit capacitor
voltage is 50 VDC or less
and disconnect the
connector X206A.
4. Caution when touching high
temperature area
Be noted that there are high
temperature areas inside the
switch box.
1
Disconnect each
connector.
2
Remove the 2 screws
to disconnect the active
module.
Step
Procedure Points