SiE25-110 Field Piping and Wiring
Field Piping and Wiring 37
Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when
stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it
will be necessary to provide a trap at an appropriate place in the riser gas piping.
Trap installation spacing
Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor
unit.
1.3 Field Wiring
Oil trap
Gas piping
Outdoor unit
Indoor unit
Liquid piping
*15m
*Marks. Install trap at
each difference in
height 15m
(S2534)