Method of Field Set (Reset after Maintenance Inspection/Repair) SiE25-110
44 Field Setting
1.4 Local Setting Mode No.
Example To set the filter sign time to “filter contamination - heavy” for all units in a group:
Set mode No. to “10,” setting switch No. to “0,” and setting position No. to “02.”
Table
Mode
No.
Note 1
Setting
Switch
No.
Setting Description Setting Position No. *Note 2
01 02 03
10
(20)
0Filter contamination - heavy /
light (Setting of operating
hours for filter sign indication)
(Change setting when
reducing filter sign indication
time to half due to quick soiling
of filter)
Ultra-Long-
Life Type
Light Approx.
10,000
hours
Heavy Approx.
5,000
hours
Long-Life
Type
Approx.
2,500
hours
Approx.
1,250
hours
Standard
Type
Approx.
200
hours
Approx.
100
hours
1 Long-life filter type (Setting of filter sign
indication time)
(Change setting when Ultra-long-life filter is
installed)
Long-Life Filter Ultra-Long-Life
Filter (1)
2 Remote control thermostat
(Set when remote control thermostat sensor
is used.)
Use Not use
3Estimation of filter operating hour
(Change setting when filter sign indication is
not used)
ON OFF
11
(21)
0 No. of Sky Air indoor units connected for
simultaneous ON-OFF multi system
(Change setting when simultaneous
operation multi system is used) *Note 3
Pair Twin Triple
2Indoor unit fan OFF when cooling/heating is
OFF
Fan OFF
4 PMV Control Permitted Prohibited
12
(22)
5 Automatic restart after power outage reset
*Note 6
OFF ON
13
(23)
0High
Ceiling
Ceiling-mounted built-in multi-
flow cassette type, Ceiling
suspended cassette type
NHS
Ceiling-suspended type,
wall-mounted type
2.7 m or Lower 2.7~3.5 m
Fan speed increase (wall-mounted type) Standard Slight Increase Normal Increase
1Air flow direction selection (Change setting
when blocking kit is installed) *Note 4
FTW
3Air flow direction adjustment (Change
setting when decorative air outlet panel is
installed)
Equipped Equipped
4 Setting of air flow direction adjustment
range
Upward Standard Downward
6External static pressure setting (To be set
according to connected duct resistance)
Standard
(Standard)
High Static
Pressure (High
Ceiling Setting)
Low Static
Pressure