Daikin FTXG25EV1BS Service Manual Page 296

  • Download
  • Add to my manuals
  • Print
  • Page
    / 323
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 295
Outdoor Unit (68 / 75 Class) SiEBE12-625
286 Removal Procedure
2.7 Removal of Four Way Valve, Solenoid Valve and Shunt
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure Points
1
Remove 1 screw of the
four way valve coil.
Reassembling precautions
1. Use non-oxidizing brazing
method. If nitrogen gas is not
available, braze the parts
speedily.
2. Avoid deterioration of the
gaskets due to carbonization
of oil inside the four way
valve or thermal influence.
For this purpose, wrap the
four way valve with wet
cloth. Splash water over the
cloth against becoming too
hot (keep it below 120°C).
In pulling the pipes, be
careful not to over-tighten
them with pliers. The pipes
may get deformed.
If the gas welding machine fails
to remove the four way valve,
take the steps below.
1. Disconnect the brazed pipe
sections that are readily
easy to separate and join
together later.
2. With a small copper tube
cutter, cut off the internal
pipes to easily take out the
four way valve.
Note:
Never use a hack saw. The
sawdust may come into the
circuit.
2
Remove 1 screw of the
solenoid valve coil.
Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
3
Place welding
protective sheet or iron
plate around the four
way valve to prevent
the flames of a gas
welding rod from
affecting the valve.
4
Heat the four brazed
points of the four way
valve. Disconnect the
point (a) first.
5
Disconnect the points
(b) and (c).
6
Disconnect the point
(d).
Page view 295
1 2 ... 291 292 293 294 295 296 297 298 299 300 301 ... 322 323

Comments to this Manuals

No comments