SiEBE12-625 Specifications
Specifications 19
50Hz 230V
Note:
1. The operating sound is based on the rear side suction inlet and the external static pressure 30 Pa.
Operating sound for under side suction inlet: [operating sound for rear side suction inlet]+6 dB.
However, when installation to which the external static pressure becomes low is carried out,
6 dB or more may go up.
Model FDKS25EAVMB FDKS35EAVMB
Rated Capacity 2.5kW Class 3.5kW Class
Front Panel Color
——
Air Flow Rates
m³/min
(cfm)
H 8.7 (307) 8.7 (307)
M 8.0 (282) 8.0 (282)
L 7.3 (258) 7.3 (258)
SL 6.2 (219) 6.2 (219)
Fan
Type Sirocco Fan Sirocco Fan
Motor Output W 62 62
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto
Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof
Running Current (Rated) A 0.48 0.48
Power Consumption (Rated) W 71 71
Power Factor % 64.3 64.3
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H×W×D) mm 200×700×620 200×700×620
Packaged Dimensions (H×W×D) mm 274×906×751 274×906×751
Weight kg 21 21
Gross Weight kg 29 29
Operation
Sound
H/M/L/SL dBA 35/33/31/29 35/33/31/29
External Static Pressure Pa 30 30
Moisture Removal L/h 1.2 1.9
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm VP20 (O.D.
φ 26 / I.D.φ 20) VP20 (O.D.φ 26 / I.D.φ 20)
Drawing No. 3D051882A 3D051884A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Page view 28