Troubleshooting SiEBE12-625
230 Service Diagnosis
Troubleshooting
Check No.06
Refer to P.242
Check No.07
Refer to P.243
Check No.09
Refer to P.244
Turn off the power and turn it on
again.
Check No. 06
Check the thermistor resistance
value.
Replace the fin thermistor.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectorsand
fan motor leads.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
(R4712)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Error again or outdoor unit
fan activated?
YES
Fin thermistor
NO
Slightly dirty
Check No. 09
Check the outdoor unit
fan or related.
Malfunctioning
Radiation fin dirty?
Too dirty
Functioning
Thermistor as
specified in its characteristic
chart?
Above 80°C?
NO
YES
NO
YES
Check the radiation fin
temperature.
Check No. 07
Check the installation condition.
WARNING
To cool down the electricals, the
outdoor unit fan getsstarted when
the radiation fin temperature rises
above 80°C and stops itself when
it dropsbelow 70°C.