Daikin BRC1E72 Installation Manual Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 72
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
English 17
If operation is not possible due to a malfunction, refer to following
Failure diagnosis method
.
After the test operation nishes, check that
error
code history is not displayed in the
Maintenance Information screen of the main menu according to the following procedure.
NOTE
7-12 Press Menu/OK button in the basic
screen. Main menu screen is dis-
played.
Select 7-13 Maintenance Information in the
main menu, and press Menu/OK
button.
Maintenance Information screen is 7-14
displayed. Check that error code
history is not displayed in the screen.
If no error code history is displayed
following this procedure the system
has normally completed the test
operation mode.
If the error code history is displayed, 7-15
conduct the failure diagnosis referring
to <Error code list> in the installation
manual of the indoor unit.
After the failure diagnosis nishes,
press and hold On/Off button for
4 seconds or longer in the Mainte-
nance Information screen to erase
the error code history.
Failure diagnosis method
Whenever the remote controller display
is blank or displays [Checking the
connection. Please stand by.],
troubleshoot the system per the items
in the Description column of the
following table.
If an error occurs, CODE is displayed in
the LCD as shown to the right.
Conduct the failure analysis referring to
<Error code list> in the installation
manual of the indoor unit.
When the unit No. which detected the
error during group control is con rmed,
refer to Chapter 8: Procedure
for Checking Error History.
<Basic screen>
127-
Cool
Return Clean the filter
Set to
68F
Press Menu/OK button.
<Main menu screen>
137-
Setting
Main Menu
Airflow Direction
Ventilation
Schedule
Off Timer
Celsius / Fahrenheit
Maintenance Information
1/2
Press Menu/OK button.
147-
157-
Error Code:U5
Indoor Model
–––
/000
Outdoor Model
–––
/000
Contact Info
0123
456
7890
Press and hold On/Off
button for 4 seconds or
longer during backlight lit.
Set temperature
28°C
Cool
Test Operat. CODE : U5
01_EN_3P243521-3D.indd 1701_EN_3P243521-3D.indd 17 9/13/2012 7:22:21 PM9/13/2012 7:22:21 PM
Page view 18
1 ... 18 19 20 ... 72

Comments to this Manuals