14 English
6-6 Press Menu/OK button. Setting
confi rmation screen is displayed.
Select 6-7 Yes and press Menu/OK
button. Setting details are
determined and fi eld settings
screen returns.
In the case of multiple setting
6-8
changes, repeat “6-3” to “6-7”.
After all setting changes are com-6-9
pleted, press Cancel button
twice.
Backlight goes out, and 6-10
[Checking the connection.
Please stand by.] is displayed
for initialization. After the
initialization, the basic screen
returns.
● Installation of optional accessories on the indoor unit may require changes to fi eld settings.
See the manual of the optional accessory.
For fi eld setting details related to the indoor unit, see installation manual shipped with the ●
indoor unit.
NOTE
Mode
No.
(Note 1)
First
Code
No.
Description
Second Code No. (Note 2)
(Items in bold are factory default settings)
01 02 03 04
10 (20)
2
Priority of thermistor
sensors for space
temperature control
The return air
thermistor is
primary and the
remote
controller
thermistor is
secondary.
The remote
controller
thermistor is not
utilized. Only
the return air
thermistor will
be utilized.
Only the
remote
controller
thermistor will
be utilized.
————
5
Room temperature
value reported to
multizone controllers
Return air
thermistor
Thermistor
designated by
10-2 above
(Note 3)
———— ————
12 (22) 2
Thermo-on/off
deadband
(Note 4)
2F (1C) 1F (0.5C) ———— ————
1c
1
Thermistor sensor for
auto changeover and
setback control by the
remote controller
Utilize the return
air thermistor
Utilize the remote
controller
thermistor
———— ————
3
Access permission
level setting
Level 2 Level 3 ———— ————
1e 2 Setback availability N/A Heat only Cool only Cool/Heat
<Setting confi rmation screen>
66-
76-
Setting
Save the settings?
Field Settings
Yes No
Press Menu/OK button.
Setting confi rmation
01_EN_3P243521-3D.indd 1401_EN_3P243521-3D.indd 14 9/13/2012 7:22:20 PM9/13/2012 7:22:20 PM