Field Setting SiENBE34-703
86 Test Operation
! Setting by pushbutton switches
The following settings are made by pushbutton switches on PC board.
(Factory setting)
There are the following three setting modes.
$ Setting mode 1 (H1P off)
Initial status (when normal) : Also indicates during “abnormal”.
% Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
& Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
! Mode changing procedure
! Mode changing procedure
H1P H2P H3P H4P H5P H6P H7P
LED indication
7787777
BS1 BS2 BS3 BS4 BS5
RESET
(V2760)
MODE
SET
RETURN
TEST
Setting mode 1
Monitor mode
H1PH1P
Setting mode 2
H1P
Push and hold the BS1
(MODE button) for 5 seconds.
(V2761)
Off
MODE
On
MODE
Push the BS1(MODE button) one time.
(Normal)
Push the BS1(MODE button)
one time.
Using the MODE button, the modes can be changed as follows.
(V2762)
(Set): Select mode with BS2 (SET button) in each selection step.
Monitor mode
Setting mode 1
(Initial condition)
Setting mode 2
Setting item selection (Set)
Setting condition
selection (Set)
Check item selection (Set)
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(MODE button).
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(MODE button).
Contents display
Press BS1 (MODE button) for more than 5 sec. Press BS1 (MODE button).