SiENBE34-703 Field Setting
Test Operation 71
3. Field Setting
3.1 Field Setting from remote control
Individual function of indoor unit can be changed from the remote control. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
3.1.1 Wired remote control <BRC1C62>
1. When in the normal mode, press the “ ” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “ ” button (2).
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), push the “ ” button (3) and select the INDOOR UNIT NO to be set. (This
operation is unnecessary when setting by group.)
4. Push the “ ” upper button (4) and select FIRST CODE NO.
5. Push the “ ” lower button (5) and select the SECOND CODE NO.
6. Push the “ ” button (6) once and the present settings are SET.
7. Push the “ ” button (7) to return to the NORMAL MODE.
(Example)
If during group setting and the time to clean air filter is set to FILTER CONTAMINATION,
HEAVY, SET MODE NO. to “10” FIRST CODE NO. to “0”, and SECOND CODE NO. to “02”.
SETTING
TEST
UNIT NO.
3
4
5
6
7
1
2
.
.
.
(V0292)
UNIT NO.
SECOND
CODE NO.
FIRST
CODE NO.
MODE NO.
FIELD
SET
MODE