SiENBE34-703 Troubleshooting by Indication on the remote control
Troubleshooting 123
3.2 A1 Indoor Unit: PC Board Defect
remote control
Display
A1
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Check data from E²PROM.
Malfunction
Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.
Supposed
Causes
! Defect of indoor unit PC board
Troubleshooting
Turn power supply OFF, then
power ON again.
Does the system
return to normal?
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
Caution
External factor other than
malfunction (for example,
noise etc.).
Replace the indoor unit PC
board.
(V2777)
NO