Daikin BRC7E61W Service Manual Page 188

  • Download
  • Add to my manuals
  • Print
  • Page
    / 266
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 187
SiENBE34-703 Troubleshooting by Indication on the remote control
Troubleshooting 177
3.46 UE Malfunction of Transmission between Central
remote control and Indoor Unit
remote control
Display
UE
Applicable
Models
AII indoor unit models
Centralized controller
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote control is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
! Malfunction of transmission between optional controllers for centralized control and indoor
unit
! Connector for setting master controller is disconnected.
! Failure of PC board for centralized remote control
! Defect of indoor unit PC board
Page view 187