Daikin BRC7E61W Service Manual Page 152

  • Download
  • Add to my manuals
  • Print
  • Page
    / 266
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 151
SiENBE34-703 Troubleshooting by Indication on the remote control
Troubleshooting 141
3.16 E4 Outdoor Unit: Actuation of Low Pressure Sensor
remote control
Display
E4
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under specific pressure.
Operating pressure:0.07MPa
Supposed
Causes
! Abnormal drop of low pressure (Lower than 0.07MPa)
! Defect of low pressure sensor
! Defect of outdoor unit PC board (A1P)
! Stop valve is not opened.
Page view 151