Daikin RXQ18P7W1BA Specifications Page 65

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 64
A new range of R-410A inverter condensing units
for multi application with air handling units.
• Inverter controlled units
Large capacity range (from 5 to 18HP)
• Cooling only
• R-410A
Control z: control of air
temperature (suction
temperature, room
temperature) via Daikin
control (no DDC controller
needed)
Large range of expansion
valve kits available
BRC1D52 is used to set
the set point temperature
(connected to the EKEXMCB).
Air handling unitAir handling unit
(Field (Field
Supply)Supply)
EKEXMCBEKEXMCB
EXV-EXV-kitkit
COMBINATION TABLE
OUTDOOR UNIT
CONTROL
BOX
EXPANSION VALVE KIT
CONTROL Z CLASS 50 CLASS 63 CLASS 80 CLASS 100 CLASS 125 CLASS 140 CLASS 200 CLASS 250
EKEXMCB EKEXV50 EKEXV63 EKEXV80 EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250
3ph
RXQ5P
XXXXXXXXX
RXQ8P
XXXXXXXXX
RXQ10P
XXXXXXXXX
RXQ12P
XXXXXXXXX
RXQ14PA
XXXXXXXXX
RXQ16PA
XXXXXXXXX
RXQ18PA
XXXXXXXXX
COOLING ONLY
RXQ-P(A)
5 8 10 12 14 16 18
Capacity range HP 5 8 10 12 14 16 18
Capacity cooling kw 14.0 22.4 28.0 33.5 40.0 45.0 49.0
Power input (Nominal) cooling kw 3.52 5.56 7.42 9.62 12.4 14.2 16.2
Dimensions HxWxD mm 1,680x635x765 1,680x930x765 1,680x1,240x765
Weight kg 157 185 238 315 323
Sound Level
sound power cooling dBA 72 78 80 83
sound pressure cooling dBA 54 57 58 60 63
Air Flow Rate (nominal at 230V) cooling m /min 95 171 185 196 233 239
Operation Range cooling min~max °CDB -5.0~43.0
Refrigerant R-410A
Power Supply 3N~/400V/50Hz
Max n° of indoor units to be connected 8 13 16 19 23 26 29
Piping connections liquid (OD)/gas mm 9.5 / 15.9 9.5 / 19.1 9.5 / 22.2 12.7 / 22.2 12.7 / 28.6 15.9 / 28.6
VRV+EXV-kit - VRV Air Handling Applications
3
p. 65
gas pipe
liquid pipe
F1, F2 communication
1602UKEPCEN07-200-artwork.indd 651602UKEPCEN07-200-artwork.indd 65 1/8/07 07:18:181/8/07 07:18:18