Automatic Charge Function
3. INSTALLATION & MAINTENANCE FRIENDLY DESIGN
Conventional Way:
1. calculation of additional refrigerant charging volume
2. charging the unit with additional refrigerant
3. measuring the weight of the cylinder
4. judgment based on pressure (test operation)
VRVIII
With VRVIII however, these 4 steps are omitted since VRVIII unit can
be charged with the necessary amount of refrigerant automatically
via a push button on the PCB. Automatic charging will cease once the
appropriate amount of refrigerant has been transferred.
If temperature drops below 20°C manual charging is necessary. After
having switched to heating and once the indoor temperature rises
above 20°C, push the auto charge button to activate auto charge
function. Refrigerant containment is only available after performing
the automatic charge function.
When refrigerant charging has ceased, pushing the test operation
button on the PCB will initiate a check on the wiring, shut off valves,
sensors and refrigerant volume. This test ceases automatically when
completed.
Automatic Test
Self Diagnostic Function
This function operated via push button on the PCB, speeds up
troubleshooting and should be used for start-up and maintenance.
Disconnected thermistors, faulty solenoid valves or motor operated
valves, compressor malfunctions, communication errors, etc can be
diagnosed quickly.
Easy Maintenance
p. 23
Outdoor temperature
Indoor temperature
1
2
3
Automatic
charge
function
Manual
charge
1602UKEPCEN07-200-artwork.indd 231602UKEPCEN07-200-artwork.indd 23 1/8/07 07:14:081/8/07 07:14:08