REYQ8P 1 2 13 100 260 30
REYQ10P 1 2 16 125 325 37
REYQ12P 1 2 19 150 390 37
REYQ14P 1 2 22 175 455 26
REYQ16P 1 2 26 200 520 26
REYQ18P 2 3 29 225 585 31
REYQ20P 2 3 32 250 650 31
REYQ22P 2 4 35 275 715 38
REYQ24P 2 4 39 300 780 38
REYQ26P 2 5 42 325 845 41
REYQ28P 2 5 45 350 910 41
REYQ30P 2 6 48 375 975 46
REYQ32P 2 6 52 400 1,040 46
REYQ34P 3 6 55 425 1,105 36
REYQ36P 3 6 58 450 1,170 36
REYQ38P 3 7 61 475 1,235 41
REYQ40P 3 8 64 500 1,300 41
REYQ42P 3 8 64 525 1,365 46
REYQ44P 3 8 64 550 1,430 46
REYQ46P 3 9 64 575 1,495 51
REYQ48P 3 9 64 600 1,560 51
VRV III
heat recovery
N° of
outdoor
units
N° of
compressors
Maximum n° of
connectable
indoor units
Minimum
capacity
index - 50%
Maximum
capacity
index - 130%
Capacity
steps
RWEYQ10M 1 1 16 125 325 22
RWEYQ20M 2 2 20 250 650 32
RWEYQ30M 3 3 32 375 975 37
VRV-WII
heat pump
VRV-WII
heat recovery
N° of
outdoor
units*
N° of
compressors
Maximum n° of
connectable
indoor units
Minimum
capacity
index - 50%
Maximum
capacity
index - 130%
Capacity
steps
10HP
Outdoor unit
p. 11
Model 20 25 32 40 50 63 71 80 100 125 200 250
Capacity index 20 25 31.5 40 50 62.5 71 80 100 125 200 250
Indoor Unit Capacity Index
eg. Selected indoor units: FXCQ25 + FXFQ100 + FXMQ200 + FXSQ40
Connection ratio: 25 + 100 + 200 + 40 = 365
9 possible outdoor unit REYQ12P
2
3
4