Outdoor Units
p. 34
RXYQ-P
Combination RXYQ8P7W1B
RXYQ10P7W1B
RXYQ12P7W1B
Nominal capacity cooling kW
heating kW
COP cooling
heating
Capacity range HP
Power input (nominal) cooling kW
heating kW
Max n° of indoor units to be connected
Indoor index connection minimum
maximum
Casing colour
material
Fan type
air flow rate cooling m
3
/min
(nominal at 230V)
heating m
3
/min
external static pressure (MAX) Pa
Compressor type
Operation range cooling minimum °CDB
maximum °CDB
heating minimum °CWB
maximum °CWB
Refrigerant type
charge kg
control
Maximum total refrigerant charge in the system kg
Refrigerant Oil type
charged Volume l
Piping Connections liquid type
diameter (OD) mm
gas type
diameter (OD) mm
heat insulation
max. total length m
Defrost method
Defrost control
Capacity control method
Capacity control [%]
Safety devices
Power supply name
phase
frequency Hz
voltage V
VRVIII HEAT PUMP - HIGH COP COMBINATION
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems,
each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
RXYQ16P7W1B RXYQ18P7W1B RXYQ20P7W1B RXYQ22P7W1B
2 1
1 2 1
1
44.8 50.4 56.0 61.5
50.0 56.5 63.0 69.0
4.04 3.88 3.78 3.62
4.27 4.15 4.09 4.04
16 18 20 22
11.1 13.0 14.8 17.0
11.7 13.6 15.4 17.1
26 29 32 35
200 225 250 275
520 585 650 715
Daikin White
Painted galvanised steel
Propeller
171 + 171 171 + 185 185 + 185 185 + 185
171 + 171 171 + 185 185 + 185 185 + 185
78Pa in high static pressure
Hermetically sealed scroll compressor
-5.0 -5.0 -5.0 -5.0
43.0 43.0 43.0 43.0
-20.0 -20.0 -20.0 -20.0
15.0 15.0 15.0 15.0
R-410A
7.7 + 7.7 7.7 + 8.4 8.4 + 8.4 8.4 + 8.6
Expansion valve (electronic type)
Less than 100 (calculated charge less than 95)
Synthetic (ether) oil
2.1 + 2.1 2.1 + 3.9 3.9 + 3.9 3.9 + 3.9
Braze connection
12.7 15.9 15.9 15.9
Braze connection
28.6 28.6 28.6 28.6
Both liquid and gas pipes
1,000 1,000 1,000 1,000
Reversed cycle
Sensor for outdoor heat exchanger temperature
Inverter controlled
~ 100 ~ 100 ~ 100 ~ 100
HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
W1 W1 W1 W1
3N~ 3N~ 3N~ 3N~
50 50 50 50
400 400 400 400
5
1602UKEPCEN07-200-artwork.indd 341602UKEPCEN07-200-artwork.indd 34 1/8/07 07:15:271/8/07 07:15:27