24
NO
OK
NG
OK
NG
OK
Is value of each temperature
thermistor close to measured
value?
Securely connect the
connectors to check
operation.
YES
Is abnormal value shown when
exceeding a certain temperature
during operation?
Repair soldering.
Replace the PC board.
Are connectors of
thermistor securely
connected?
Is PC board soldered
properly? (connector
section of thermistor)
NG
Replace the thermistor.
Malfunction 7-9: Error code “C4”,”C9”,”J6”,”H9” (Malfunction of
thermistors) is displayed.
Possible
causes
Ԙ Faulty thermistor
ԙ Disconnection of connector
Ԛ Poor soldering of PC board
ԛ Faulty PC board
(Reference)
This malfunction is automatically reset. If the malfunction is present even in stop mode,
disconnection of thermistor, poor soldering inside PC board, or affixed foreign matter, etc. are
presumed. Judge by measuring the resistance of thermistor. If the malfunction has been reset when
servicing, operate the unit while comparing the actual temperature measured at the thermistor
position to the reading of the transmission monitor to check for the difference in temperature.