Daikin FT25JV1B Installation Manual Page 26

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
25
NO
YES
NO
NG
OK
NO
NG
OK
Is value of each temperature thermisto
r
close to measured value?
Replace the thermistor. (If the
malfunction is not remedied even
when the thermistor is replaced,
replace the PC board.)
YES
Does refrigerant leak?
Repair the leaking point and
charge the specified amount of
refrigerant
Change the set temperature. Do pressure,
pipe temperature, andǍT㧔㧖㧕vary properl
y
in accordance with the change of the
compressor operating frequency?
Check refrigerant circuit once again.
Does the faulty
compression occur?
(Conduct pump down
operation to check.)
Is refrigerant circuit clogged?
YES
Repair the clogged point of
refrigerant circuit.
Replace the
compressor
Malfunction 7-10: Error code “U0” (Refrigerant shortage) is displayed.
Possible
causes
Ԙ Refrigerant shortage
ԙ Clogged refrigerant circuit
Ԛ Faulty thermistor
ԛ Faulty compressor (inverter type only)
Ԝ Faulty PC board
“U0” is decided when the compressor operating frequency exceeds a certain frequency (that varies depending
on the model) while low current continues or when there is no difference in temperature between indoor and
outdoor heat exchangers. Measure the compressor operating frequency and temperature of each section with
the transmission monitor, and actual value of current, temperature at the thermistor section, gas pressure, etc.
to compare the values and probe the causes.
㧔㧖㧕 Difference between the suction and discharge temperatures of indoor unit
Page view 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31

Comments to this Manuals

No comments