Is correct voltage supplied to bot
h
indoor and outdoor units?
Recheck the power supply.
NO
Disconnect No.2 transmission wire (Note) fro
m
outdoor unit terminal board. Is outdoor unit dat
a
displayed with transmission monitor connected?
Faulty transmission wire.
Replace the transmissio
n
wire or remedy the fault
y
Replace the outdoor unit PC boar
d
(faulty data sending)
Is indoor unit data displayed with
connection of No.2 wire while
transmission monitor unchanged
connected?
Replace indoor unit PC board.
(Faulty data sending or receiving)
Is outdoor unit data displayed wit
h
transmission monitor connected to
indoor unit?
Malfunction 7-7: Error code “U4” (Transmission error between indoor and
outdoor units) is displayed.
Possible
causes
Ԙ No power supply to indoor or outdoor unit
ԙ Disconnection in transmission wire between indoor and outdoor units, short circuit,
poor insulation between phases, poor insulation unit and ground, incorrect wiring
Ԛ Faulty indoor unit PC board (Faulty data sending or receiving of indoor unit )
ԛ Faulty outdoor unit PC board (Faulty data sending or receiving of outdoor unit)
Outdoor unit sends the data independently.
If the data displayed, outdoor unit PC boar
d
sends the data normally.
If indoor unit data can
displayed, transmission wire is
OK.