SiBE12-713 Troubleshooting
Service Diagnosis 267
5.23 Radiation Fin Temperature Rise
Remote
Controller
Display
L4
Outdoor Unit LED
Display
A
5
1
1
2
1
3
1
4
4
Method of
Malfunction
Detection
A radiation fin temperature rise is detected by checking the radiation fin temperature being
detected by the fin thermistor with the compressor on.
Malfunction
Decision
Conditions
๎
The radiation fin temperature with the compressor on is above 103ยฐC.
๎
The error is cleared when the temperature drops below 95ยฐC.
๎
If a radiation fin temperature rise takes place 255 times successively, the system will be shut
down.
๎
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
๎
Fin temperature rise due to defective outdoor unit fan
๎
Fin temperature rise due to short-circuit
๎
Fin thermistor defective
๎
Connector in poor contact
๎
Outdoor unit PCB defective