Troubleshooting SiBE12-713
266 Service Diagnosis
Troubleshooting
Check No.07
Refer to P.280
Check No.09
Refer to P.281
Turn off the power and turn it on
again.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
(R5147)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Error again or outdoor unit
fan activated?
YES
NO
Slightly dirty
Check No. 09
Check the outdoor unit
fan or related.
Malfunctioning
Radiation fin dirty?
Too dirty
Functioning
Above 100˚C?
NO
YES
Check the radiation fin
temperature.
Check No. 07
Check the installation condition.
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 100˚C and stops itself
when it drops below 85˚C.