Page view 5
Figure 2: Operator Interface Trend History Screen
The controller memory (no batteries required) also retains
the fault history for troubleshooting and monitoring unit
performance. A time/date stamp is associated with each fault.
The fault history can be downloaded through the USB port.
RapidRestore
®
Mission critical facilities such as data centers and hospitals
are demanding stringent capabilities for chillers to restart and
reach full load operation quickly in the event of a power loss.
With the capability of RapidRestore
®
, Magnitude
®
model WMC
chillers are engineered to meet those needs. See Table 1
below for specications.
Table 1: WMC RapidRestore
®
Times- After Power
Restoration
Compressor Start Fast Loading to 80% Load
43 sec 120 sec*
* Estimated load time. Times may vary depending on operating conditions.
Open Choices
BAS Flexibility
The exclusive Open Choices
feature provides seamless
integration and comprehensive monitoring, control, and
two-way data exchange using industry standard protocols
LonTalk
®
, BACnet
®
or Modbus
®
. Open Choices
offers simple
and inexpensive exibility to use the Building Automation
System (BAS) of your choice without an expensive gateway
panel. Open Choices
benets include:
Easy to integrate into your BAS of choice
Factory- or eld-installed communications module
Integrated control logic for factory options
Easy-to-use local user interface
Comprehensive data exchange
Certications and Standards
As with many other Daikin Applied chiller products, the
Magnitude
®
model WMC meets all necessary certications
and standards.
AHRI Certication
Part load performance can be presented in terms of Integrated
Part Load Value (IPLV), which is dened by AHRI Standard
550/590. Based on AHRI Standard 550/590, and as shown
in Figure 3, a typical chiller can operate up to 99% of the time
at off-peak conditions and usually spends most of this time at
less than 60% of design capacity.
Figure 3: IPLV Dened by AHRI Standard 550/590
WMC chillers are rated and certied to AHRI Standard
550/590. The ability of the WMC chillers to achieve very high
part load efciencies, as evidenced by their world-class IPLV
ratings, is due primarily to the use of a variable frequency
drive and the low friction of the magnetic bearing system. For
more information on variable frequency drives, see Integrated
Variable Frequency Drive on page 5.
RapidRestore
®
Quickly restores cooling capacity
when power is restored after a power failure
Compressor Start – Amount of time required for
the chiller to restart
Fast Loading – Amount of time required for the
chiller to reach a certain load condition
0
10
20
30
40
50
100
75
50
25
1 Percent
42 Percent
45 Percent
12 Percent
Percent Ton-Hour Weighting
CAT 602-4 • MAGNITUDE
®
MODEL WMC CHILLERS 6 www.DaikinApplied.com