Catalog 602-4Magnitude®Magnetic Bearing Centrifugal ChillersModel WMC C Vintage 145 to 400 Tons (500 to 1400 kW) HFC-134a Refrigerant

Page 2 - Table of ConTenTs

Unit OptionsExport PackagingA wooden skid that aids in moving the unit and tight tting plastic covering the entire unit to protect it from dirt and g

Page 3 - Features and Benets Summary

RapidRestore®Allow chillers to restart and reach full load operation quickly in the event of a power loss event. See RapidRestore® on page 6 for more

Page 4 - The Compressor Technology

Figure 7: Refrigeration System Diagram BUBBLE NO.LABELVALVE CONTROL1 PRESSURE TAP N/A2 RELIEF VALVE MANUAL3 RELIEF VALVE AUTOMATIC4 SERVICE

Page 5 - The Control Technology

Location RequirementsDaikin WMC units are designed only for indoor, weather-protected, non-freezing areas consistent with the NEMA 1 rating on the chi

Page 6 - Certications and Standards

temperature entering on start-up must not exceed 90°F (32°C). Evaporator Leaving Water TemperatureWarmer leaving chilled water temperatures will raise

Page 7 - Factory Testing

Condenser Pumps and PipingThe condenser water pump(s) must be cycled off when the last chiller of the system cycles off. This will keep cold condenser

Page 8 - Unit Dimensions

applICaTIon ConsIderaTIonsCAT 602-4 • MAGNITUDE® MODEL WMC CHILLERS 16 www.DaikinApplied.comType B Knockdown, “Partial Disassembly”Compressor(s), pow

Page 9 - Drawing Notes

www.DaikinApplied.com 17 CAT 602-4 • MAGNITUDE® MODEL WMC CHILLERSengIneerIng guIde speCIfICaTIonsMAGNITUDE® MAGNETIC BEARING CENTRIFUGAL CHILLERSPAR

Page 10 - Electrical Options

centrifugal chiller. Chillers shall have no more than two oil-free, magnetic bearing, semi-hermetic centrifugal compressors (no exceptions). Each comp

Page 11 - Special Order Options

3. The chiller shall be equipped with a refrigerant cooled and integrated Variable Frequency Drive (VFD) to automatically regulate compressor speed i

Page 12 - FLOW CHART LEGEND

©2014 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in d

Page 13 - Location Requirements

system consisting of a 15-inch VGA touch-screen operator interface and a unit controller. 2. The touch-screen shall display the unit operating parame

Page 14

5. OSHPD Certication: The chiller shall be OSHPD Pre-Approved per OSP–0116-10 and be so labeled. The chiller shall meet a minimum seismic design spe

Page 17 - MAGNITUDE

CAT 602-4 ©2014 Daikin Applied (4/14) | (800) 432–1342 | www.DaikinApplied.comDaikin Applied Training and DevelopmentNow that you have made a

Page 18 - Overall

Technology That Just Makes Sense The industry’s next generation of centrifugal chillers is here today with Daikin Magnitude® chillers. The new techno

Page 19

The Compressor TechnologyModel WMC’s exceptional efciency and reliability is due to its cutting-edge magnetic bearing compressor technology. A digita

Page 20 - 2.5. OPTIONAL ITEMS

Additional Compressor Design BenetsModel WMC’s magnetic bearing compressor design offers many benets not only because of its oil free design but als

Page 21 - PART 3 - EXECUTION

Figure 2: Operator Interface Trend History Screen The controller memory (no batteries required) also retains the fault history for troubleshooting a

Page 22

Compliance with ASHRAE Std. 90.1ASHRAE Standard 90.1 was developed to assist owners and designers make informed choices on a building’s design, system

Page 23

Unit DimensionsFigure 4: WMC145S (2-pass, right-hand conguration, with grooved connections) Figure 5: WMC145-400D (2-pass, right-hand conguration

Page 24

Drawing Notes1. Final connections must allow for 0.5 inch +/- (12.7mm) manufacturing tolerances.2. 1.00-inch FPT (25.4 mm) evaporator and condenser