operaTIon
IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS 46 www.DaikinApplied.com
Problem Alarms
Problems do not cause compressor shutdown but do limit operation of the chiller.
Table 14: Unit Problem Alarms
Description OITS Alarm Message Alarm Reset
Condenser Water Freeze Protect Comp 1 COND PUMP ON - Condenser Pressure Low (Freeze) Auto-clears
Condenser Water Freeze Protect Comp 2 COND PUMP ON - Condenser Pressure Low (Freeze) Auto-clears
Low Evaporator Pressure - Inhibit Loading Circuit 1 NO LOAD - Evaporator Pressure Low Auto-clears
Low Evaporator Pressure - Inhibit Loading Circuit 2 NO LOAD - Evaporator Pressure Low Auto-clears
Low Evaporator Pressure - Unload Circuit 1 UNLOAD - Evaporator Pressure Low Auto-clears
Low Evaporator Pressure - Unload Circuit 2 UNLOAD - Evaporator Pressure Low Auto-clears
Ground Fault Protection 1 COMPR STOP - Ground Fault Locked off (requires local reset)
Ground Fault Protection 2 COMPR STOP - Ground Fault Locked off (requires local reset)
Warning Alarms
Warnings only generate a warning message to the operator. Chiller operation is not affected.
Table 15: Unit Warning Alarms
Description OITS Alarm Message Alarm Reset
Entering Condenser Water Temperature Sensor Fault NO ACTION - Condenser EWT Out of Range Auto-clears
Entering Evaporator Water Temperature Sensor Fault NO ACTION - Evaporator EWT Out of Range Auto-clears
Liquid Line Refrigerant Temperature Sensor Fault NO ACTION - Liquid Line Temp Out of Range Auto-clears
Leaving Condenser Water Temperature Sensor Fault NO ACTION - Condenser LWT Out of Range Auto-clears
Condenser Pump #1 Fault No Alert shown on OITS panel No Alarm
Condenser Pump #2 Fault No Alert shown on OITS panel No Alarm
High Discharge Temperature Comp 1 No Alert shown on OITS panel No Alarm
High Discharge Temperature Comp 2 No Alert shown on OITS panel No Alarm
Entering Evap Temperature Sensor Fault (EWT reset active) No Alert shown on OITS panel No Alarm
Chiller Running with Limited Capacity No Alert shown on OITS panel No Alarm
Load Balance Valve Fault 1 COMPR WARNING - Flooded Compressor Operator Cleared Only
Load Balance Valve Fault 2 COMPR WARNING - Flooded Compressor Operator Cleared Only
Table 16: Compressor Warning Alarms
Description OITS Alarm Message Alarm Reset
Repower After Power Loss 1 COMPR STOP - Line Voltage Low Auto-clears
Repower After Power Loss 2 COMPR STOP - Line Voltage Low Auto-clears