www.DaikinApplied.com 23 IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
operaTIon
Table 4: COMPRESSOR STATUS Possibilities
Complete STATUS Text
(in priority sequence)
Notes
OFF Manual Switch
Reason for the compressor being off
OFF Compressor Alarm
OFF Unit State
OFF Evap Flow/Re-circulate
OFF Start to Start Timer=xxx
OFF Stop to Start Timer=xxx
OFF Staging (Next ON)
OFF Awaiting Load
RUN Unload Vanes-Max Amps
Overrides water temperature
command
RUN Hold Vanes-Max Amps
RUN Load
Normal operationRUN Hold
RUN Unload
SHUTDOWN Unload
Unloading during the shutdown
sequence
NOTE: Timer countdown values will be shown where “xxx” is
shown in Table 4.
(III) Action Buttons
Chiller Control: AUTO button (normal start) and STOP
button (normal shutdown). These buttons are only
visible and active when the control is in the “Local”
mode. This eliminates the possibility of inadvertently
shutting off the unit locally when it is under control of
a remote signal such as a BAS. The rest of the screen
images shown in this manual will not display the AUTO
and STOP buttons; however, they will be visible on the
actual OITS if in “Local” mode.
HISTORY button: Toggles between the Trend History
Screen (Figure 49 on page 41) and the Alarm History
Screen (Figure 50 on page 42).
VIEW button: Shows details about the unit status and
conditions. Pressing this button will toggle between the
Home View Screen (Figure 16) and the Detail View
Screen (Figure 17).
SET button: Toggles between the Setpoint Screens
(descriptions start on page 26) that are used for
changing setpoints and the Service Screen (Figure 47 on
page 40).
Detail View Screen
Pressing the VIEW button on the bottom of the Home View
Screen accesses the Detail View Screen, shown in Figure 17.
The Detail View Screen can also be accessed by pressing the
VIEW button from any other screen that contains the VIEW
button.
Figure 17: Detail View Screen
Data for one compressor is shown at a time on the Detail
View Screen. Pressing the COMP button in the lower-left hand
corner of the screen will toggle between compressor #1 and
compressor #2.
When rst booted up, the Detail View Screen will be blank on
the right side, as shown in Figure 17. Various information will
appear on the right side of the Detail View Screen by pressing
available buttons. For example, pressing the STATE button
will bring up a display of the Compressor State Information, as
shown in Figure 18, on the right side of the Detail View Screen.
Use the COMP button to toggle between the two compressors’
data.
Figure 18: Compressor State Information