Daikin RXQ18P7W1BA Installation Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
RX(Y)Q5-10-12P7W1B + RXQ8P7W1B + RXYQ8P8W1B +
RXYHQ12P8W1B + RX(Y)Q14~18P7W1BA
VRVIII System air conditioner
4PW48461-1
Installation manual
18
9. PIPE INSULATION
After finishing the leak test and vacuum drying, the piping must be
insulated. Take into account the following points:
Make sure to insulate the connection piping and refrigerant
branch kits entirely.
Be sure to insulate liquid and gas piping (for all units).
Use heat resistant polyethylene foam which can withstand a
temperature of 70°C for liquid side piping and polyethylene foam
which can withstand a temperature of 120°C for gas side piping.
Reinforce the insulation on the refrigerant piping according to
the installation environment.
Condensation might form on the surface of the insulation.
If there is a possibility that condensation on the stop valve might
drip down into the indoor unit through gaps in the insulation and
piping because the outdoor unit is located higher than the indoor
unit this must be prevented by sealing up the connections. See
figure 9.
For cooling only units, insulation which can withstand 70°C is
also sufficient for gas side piping.
10. CHECKING OF UNIT AND INSTALLATION
CONDITIONS
Be sure to check the following:
The piping work
1 Make sure piping size is correct.
See "6.2. Selection of piping material" on page 5.
2 Make sure insulation work is done.
See "9. Pipe insulation" on page 18.
3 Make sure there is no faulty refrigerant piping.
See "6. Refrigerant piping" on page 5.
The electrical work
1 Make sure there is no faulty power wiring or loose nuts.
See "8. Field wiring" on page 12.
2 Make sure there is no faulty transmission wiring or loose nuts.
See "8. Field wiring" on page 12.
3 Make sure the insulation resistance of the main power circuit is
not deteriorated.
Using a megatester for 500 V, check that the insulation
resistance of 2 M or more is attained by applying a voltage of
500 V DC between the power terminals and earth. Never use
the megatester for the transmission wiring (between outdoor
and indoor unit, outdoor and COOL/HEAT selector, etc.).
11. CHARGING REFRIGERANT
The outdoor unit is factory charged, but depending on the length of
the piping when installed, the outdoor unit may require additional
charging.
For charging the additional refrigerant follow the procedure as
described in this chapter.
11.1. Important information regarding the
refrigerant used
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A
GWP
(1)
value: 1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
■➀ the factory refrigerant charge of the product,
■➁ the additional refrigerant amount charged in the field and
■➀+the total refrigerant charge
on the fluorinated greenhouse gases label supplied with the product.
The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).
(2)
In case of multiple outdoor systems, only 1 label must be adhered,
mentioning the total factory refrigerant charge of all outdoor units
connected on the refrigerant system.
Ambient temperature Humidity Minimum thickness
30°C 75% to 80% RH 15 mm
>30°C 80 RH 20 mm
1 Gas line stop valve
2 Liquid line stop valve
3 Service port for adding refrigerant
4 Sealing up treatment
5 Insulation
6 Indoor -outdoor interconnection piping
Be sure to insulate local pipes, as touching them can
cause burns.
Refrigerant can not be charged until all field wiring and
field piping has been completed.
Refrigerant may only be charged after performing the leak
test and the vacuum drying.
The refrigerant charge of the system must be less than
100 kg. This means that in case the calculated refrigerant
charge is equal to or more than 95 kg you must divide your
multiple outdoor system into smaller independent systems,
each containing less than 95 kg refrigerant charge.
For factory charge, refer to the unit name plate.
NOTE
National implementation of EU regulation on certain
fluorinated greenhouse gases may require to provide
the appropriate official national language on the unit.
Therefore, an additional multilingual fluorinated
greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of
that label.
3
5
6
2
1
4
1 factory refrigerant
charge of the product:
see unit name plate
(2)
2 additional refrigerant
amount charged in the
field
3 total refrigerant charge
4 Contains fluorinated
greenhouse gases
covered by the Kyoto
Protocol
5 outdoor unit
6 refrigerant cylinder
and manifold for
charging
Page view 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 37 38

Comments to this Manuals

No comments