This unit has a reverse phase detection circuit. (If it is activated,
only operate the unit after correcting the wiring.)
Power supply wires must be attached securely.
If the power supply has a missing or wrong N-phase, equipment
will break down.
Make sure that all wiring is secure, the specified wires are used,
and no external forces act on the terminal connection or wires.
Improper connections or installation may result in fire.
When wiring the power supply and connecting the remote
controller wiring and transmission wiring, position the wires so
that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric
shocks, fire, or overheating of the terminals.
8.5. System examples
(See figure 15)
8.6. Leading power line and transmission line
Be sure to let the power line and the transmission line pass
through a conduit hole.
Lead the power line from the upper hole on the left side plate,
from the front position of the main unit (through the conduit hole
of the wiring mounting plate) or from a knock out hole to be
made in the unit's bottom plate. (See figure 18)
Precautions when knocking out knockout holes
To punch a knockout hole, hit on it with a hammer.
After knocking out the holes, we recommend you paint the
edges and areas around the edges using the repair paint to
prevent rusting.
When passing electrical wiring through the knockout holes,
remove any burrs from the knockout hole edges. Wrap the wiring
with protective tape in order to prevent damage to the wires, put
the wires through field supplied protective wire conduits at that
location, or install suitable field supplied wire nipples or rubber
bushings into the knockout holes.
1 Field power supply
2 Main switch
3 Earth leakage breaker
4 Outdoor unit
5 Indoor unit
6 Remote controller
Power supply wiring (sheathed cable) (230 V)
Transmission wiring (sheathed cable) (16 V)
1 Electric wiring diagram. Printed on the back of the electric box lid.
2 Power wiring and ground wiring between outdoor units (inside
conduit)
(When the wiring is routed out through the lateral panel.)
3 Transmission wiring
4 Pipe opening
5 Conduit
6 Power wiring and ground wiring
7 Cut off the shaded zones before use.
8 Through cover
1 Knockout hole
2 Burr
3 If there are any possibilities that small animals enter the system
through the knockout holes, plug the holes with packing materials
(to be prepared on-site).
Use a power wire pipe for the power wiring.
Outside the unit, make sure the weak low voltage
electric wiring (i.e. for the remote control, between
units, etc.) and the high voltage electric wiring do not
pass near each other, keeping them at least 50 mm
apart. Proximity may cause electrical interference,
malfunctions, and breakage.
Be sure to connect the power wiring to the power
wiring terminal block and secure it as described under
"8.8. Field line connection: power wiring" on page 17.
Inter-unit wiring should be secured as described in
"8.7. Field line connection: transmission wiring and
cool/heat selection" on page 16.
Secure the wiring with the accessory clamps so
that it does not touch the piping and no external
force can be applied to the terminal.
Make sure the wiring and the electric box lid do not
stick up above the structure, and close the cover
firmly.