Ventilation • ERQ-AW1
7
Outdoor Unit • ERQ-AW1
4 Selection procedure
4 - 1 Selection Procedure
3TW27232-7
Integrated heating capacity coefficient
The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting operation is in progress.
The capacity values, which take these factors into account, in other words, the integrated heating capacity values, can be calculated as follows
Formula:
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation (kW) = C
A=BxC
Correction factor for finding integrated heating capacity
ERQ-AW1
Inlet port temperature of heat exchanger (°C/RH 85%) -7 -5 -3 0357
Integrating correction factor for frost accumulation 0,96 0,93 0,87 0,81 0,83 0,89 1,0
Please note that, when there is an accumulation of snow against the outside surface of the outdoor unit heat
exchanger, there will always be a temporary redusion in capacity, although this will of course vary in degree in
accordance with a number of other factors, such as the outdoor temperature (°CDB), relative humidity (RH) and
the amount of frosting which occurs.
Note:
1. The figures shows that the integrated heating capacity
expresses the integrated capacity for a single cycle (from
defrost operation to defrost operation) in terms of time.
Defrosting operation
Defrosting operation
Time
One cycle
Heating capacity