3
6
Ventilation • ERQ-AW1
21
Outdoor Unit • ERQ-AW1
6 Capacity tables
6 - 3 Capacity Correction Factor
3TW32032-2
ERQ-AW1
125 Class
Correction factor for piping length (α)
Cooling
Notes:
1 These figures illustrate the correction factor for piping length of the system at maximum load under
standard conditions.
Under patrial load conditions there is only minor deviation from the correction factor shown in the figures
above.
2 Method of calculating cooling capacity (max. capacity)
Cooling capacity = Cooling capacity obtained from the cooling capacity characteristics table X Capacity
correction factor
3 Method of calculating heating capacity (max. capacity)
Heating capacity= Heating capacity obtained from the heating capacity characteristics tableX Capacity
correction factor
Explanation of symbols:
Hp: Level difference between air handling unit and outdoorunit when
air handling unit is installed below the outdoor unit
Hm: Level difference between air handling unit and outdoorunit when
air handling unit is installed above the outdoor unit
L: Equivalent piping length (m)
α: Capacity correction factor
Diameter of pipes:
Outdoor unit class
Gas Liquid
125 J15.9 J9.5
200 J19.1 J9.5
250 J22.2 J9.5
200 Class
250 Class
Correction factor for piping length (α)
Heating
125,200,250Class