Indoor Units • 600X600 4-WAY BLOW CEILING MOUNTED CASSETTE • FXZQ-M8V1B
1 Specifications
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7,5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6° CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
1-2 ELECTRICAL SPECIFICATIONS FXZQ20M8V1B FXZQ25M8V1B FXZQ32M8V1B FXZQ40M8V1B FXZQ50M8V1B
Power Supply Name V1
Phase 11111
Frequency Hz 50 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.80 0.80 0.80 0.80 0.90
Maximum fuse amps (MFA) A 15.00 15.00 15.00 15.00 15.00
Full load amps (FLA) A 0.60 0.60 0.60 0.60 0.70
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA<= 4 x FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books”.
Finally, click on the document title of your choice.
1-1 TECHNICAL SPECIFICATIONS FXZQ20M8V1B FXZQ25M8V1B FXZQ32M8V1B FXZQ40M8V1B FXZQ50M8V1B