Indoor Units • 600X600 4-WAY BLOW CEILING MOUNTED CASSETTE • FXZQ-M8V1B
•VRV
®
Systems • Indoor Units
8
6 Dimensional drawing & centre of gravity
6 - 1 Dimensional drawing
FXZQ-M8
3D039005B
Note 2
Drain connection side
Pipe connection side
Arrow view
Suspention bolt
Adjustable (0~545)
45 or less 45 or less
Note 4
180
1,500 or more
(Required space)
From the floor side
2,500 or more
For height installation
295 or more
• Decoration panel
BYFQ60B7W1 White Ral 9010
300 or less
585~660 (Ceiling opening space)
533 (Suspention position)
533 (Suspention position)
585~660 (Ceiling opening space)
4-M4 Hole
Ceiling
Arrow view
Outdoor air intake
(Direct connection)
• Required space
1,500mm or more*
1,500mm or more*
1,500mm or more*
1,500mm or more*
* When the discharge grill is closeout the
required space is 200mm or more
NOTES
1 Location of manufacturer’s label
Indoor unit: on the bell mouth, inside suction panel
Decoration panel: on the inner frame, inside suction grille
2 When using an infrared remote control, this position will be a signal receiver.
Refer to the drawing of the infrared remote control for more details
3 When the temperature and humidity in the ceiling exceed 30°C and RH is 80 %,
or the fresh air is inducted into the ceiling, or the unit continues 24 hour
operation, an additional insulation is required (thickness 10mm or more or glass
wool or polyethylene foam)
4 Though the installation is acceptable up to maximum 660mm square ceiling
opening, keep the clearance of 45mm or less between the main unit and the
ceiling opening so that the panel overlap allowance can be ensured.
Nr Part name Description
1 Liquid pipe connection ø6.4 Flare connection
2 Gas pipe connection ø12.7 Flare connection
3 Drain pipe connection VP25 (O.D. ø32)
4 Wire intake
5 Interunit wiring connection
6 Grounding terminal Inside switch box (M4)
7Discharge
8 Air suction grille
9 Long life filter
10 Suspension bolt
FXZQ-M8
3D041038
1
2
3
A
700
700
A Arrow view
62.5 62.5
575
62.5 62.5
575
105
143
245
(140)
255 or more
15
40
Dimension between
the bottom surface
of indoor unit and
the surface of ceiling
Thickness
of panel spacer
Nr Name Description
1 Indoor unit
2 Decoration panel
3 Panel spacer