Split Sky Air • Outdoor Units
7
Outdoor Units • R-410A • RXG-E2V1B
4 Capacity tables
4 - 1 Cooling/Heating capacity tables
RXG + FTXG25E
Cooling 50Hz 220-240V
60Hz 220-230V
AFR 7.4
BF 0.18
Indoor Outdoor temperature (°C)
EWB EDB 20 25 30 32 35 40
(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.50 1.84 0.46 2.44 1.82 0.52 2.33 1.76 0.57 2.28 1.74 0.59 2.21 1.70 0.61 2.10 1.64 0.66
16.0 22 2.68 1.84 0.48 2.56 1.79 0.52 2.44 1.73 0.57 2.40 1.71 0.59 2.33 1.68 0.62 2.21 1.63 0.66
18.0 25 2.79 1.93 0.48 2.68 1.88 0.53 2.56 1.82 0.57 2.51 1.80 0.59 2.44 1.77 0.62 2.33 1.72 0.66
19.0 27 2.85 2.03 0.48 2.73 1.98 0.53 2.62 1.93 0.57 2.57 1.91 0.59 2.50 1.88 0.62 2.38 1.83 0.67
22.0 30 3.02 1.95 0.49 2.91 1.91 0.53 2.79 1.87 0.58 2.74 1.85 0.60 2.67 1.82 0.62 2.56 1.78 0.67
24.0 32 3.14 1.90 0.49 3.02 1.86 0.54 2.90 1.82 0.58 2.86 1.81 0.60 2.79 1.78 0.63 2.67 1.74 0.67
Heating 50Hz 220-240V
60Hz 220-230V
AFR 7.7
Indoor Outdoor temperature (°CWB)
EDB -10 -5 0 6 10
(°C) TC PI TC PI TC PI TC PI TC PI
16.0 2.27 0.70 2.65 0.74 3.03 0.77 3.49 0.81 3.80 0.84
18.0 2.22 0.71 2.60 0.74 2.99 0.78 3.45 0.82 3.75 0.84
20.0 2.17 0.72 2.56 0.75 2.94 0.78 3.40 0.83 3.71 0.85
21.0 2.15 0.72 2.53 0.75 2.92 0.79 3.38 0.83 3.68 0.86
22.0 2.12 0.72 2.51 0.76 2.89 0.79 3.35 0.83 3.66 0.86
24.0 2.08 0.73 2.46 0.77 2.85 0.80 3.31 0.84 3.61 0.87
3D045218B
SYMBOLS
AFR : Air flow rate (m
3
/min)
BF : Bypass factor
EWB : Entering wet bulb temp. (°CWB)
EDB : Entering dry bulb temp. (°CDB)
TC : Total cooling capacity (kW)
SHC : Sensible heating capacity (kW)
PI : Power input (kW)
NOTES
1 Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2 shows nominal (rated) capacities and power input.
3 TC, PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should not be used for
calculation.)
4 SHC is based on each EWB and EDB
SHC1 for any indoor dry-bulb temperatures (EDB1) shall be
calculated by the following formula.
SHC*: Correction value of SHC matched with the differential of EDB
and EDB1.
SHC*=0.02 X AFR(m
3
/min.) X (1-BF) X (EDB1-EDB)
The calculation value of SHC1 = SHC + SHC*
5 Capacities are based on following conditions:
Corresponding refrigerant piping length: 7.5 m
Level difference: 0 m
6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.