Split Sky Air • Outdoor Units
5
Outdoor Units • R-410A • RXG-E2V1B
3 Electrical data
RXG+FTXG-E
Representative unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit
Hz-volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FTXG25EV1BW RXG25E2V1B
50 - 220
Max. 50Hz 264V
Min. 50Hz 198V
12 15 49
3.3
35
0.23
40
0.52
50 - 230 3.2 0.22 0.50
50 - 240 3.1 0.21 0.48
FTXG25EV1BS RXG25E2V1B
50 - 220
Max. 50Hz 264V
Min. 50Hz 198V
12 15 49
3.3
35
0.23
40
0.52
50 - 230 3.2 0.22 0.50
50 - 240 3.1 0.21 0.48
3D045220B
SYMBOLS
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps (A)
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps (A)
W : Fan Motor Rated Output (W)
RHz : Rated operating frequency(Hz)
NOTES
1 RLA is based on the following conditions:
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 35°CDB
2 Maximum allowable voltage variation between phases is 2%
3 Select wire size based on the larger value of MCA.
4 Instead of fuse, use circuit breaker
5 For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’.
Finally, click on the document title of your choice.