• Control systems
• intelligent Touch Manager • ED721208
2) Counting the electricity at the stopped condition of the unit
Even if a VRV is stopped or in the condition of thermostat -OFF (the condition that the compressors are stopped as the temperature
in the space where all the indoor units are installed falls down to the set temperature), the VRV consumes energy due to the energy
consumption mainly by the crankcase heater in the outdoor unit.
When the iTM is used, the rated power consumption of the crankcase heater is divided by the number of indoor units in usual
connection (for instance, two indoor units of 2.5 HP are connected to an outdoor unit of 5 HP etc.) and the value is registered at the
test operation, adapting each indoor unit’s capacity.
(Example)
RXYQ5P
(Crankcase heater's output=50W)
FXFQ80P×2
(Power consumption at no operation=50/2=25W)
The iTM counts the indoor units operating conditions every 20 seconds.
SincetheindoorunitssendON/OFFdataofthecrankcaseheatertoiTM,itaddsone(+1)tothepowercounterinsideiTMatno
operation of the air-conditioner when the crankcase heater is ON.
When this counter reaches 180, it judges that the crankcase heater was ON for one hour, and in case of the above mentioned indoor
unit, the counter goes back to zero after 25 Wh is added to the counting result.
This calculation process is conducted separately from the proportional division computation mentioned on this section, and this input
is got rid of from the pulse input of the watthour meter. Because of this procedure, the power consumption in the space where the
air-conditioner is not used at all is counted constantly every month.
(However, as this air-conditioning system is a multi-system, in case that one outdoor unit is shared to another tenant, the count output
can be seen in lower value rather than the crankcase heater’s power consumption registered, because the crankcase heater does not
actuate when another tenant operates the VRV.)