Installation Settings
The Installation Settings let you congure
the equipment connected to the Daikin ENVi
thermostat.
Allow Auto Heat/Cool
Enabling this option allows the user to select
auto change-over as a system mode.
Only visible if the Indoor Unit supports heat or an
auxiliary heat source is congured.
Heat/Cool Min Delta
Sets the minimum dierence between the heat
mode set temperature and the cool mode set
temperature when the system mode is in auto-
changeover. The delta is adjustable from 2 to 10
°F (1.1 to 5.5 °C). The default value is 5 °F (2.8 °C).
Only visible if the Indoor Unit supports heat or an
auxiliary heat source is congured.
System Settings
The System Settings let you congure general
heat pump settings.
Min Cycle O Time Sets the minimum
equipment o time between cycles: 240 to
900 seconds (default is 240 seconds).
Min Cycle On Time Sets the minimum
equipment run time in cool mode: 1 to 20
min (default is 3 min).
Min Outdoor Temp Disables the compressor
when the outside air temperature reaches
the congured minimum setting. This
performs two functions. It prevents the
compressor from running when the outdoor
temperature is too low, thus resulting in
To congure the
system settings:
From the Home screen,
press MENU.
Select Settings ▶
Installation Settings.
Congure the devices
connected to the
thermostat.