Installation Settings
The Installation Settings let you congure
the equipment connected to the Daikin ENVi
thermostat.
Allow Auto Heat/Cool
Enabling this option allows the user to select
auto change-over as a system mode.
Only visible if the Indoor Unit supports heat or an
auxiliary heat source is congured.
Heat/Cool Min Delta
Sets the minimum dierence between the heat
mode set temperature and the cool mode set
temperature when the system mode is in auto-
changeover. The delta is adjustable from 2 to 10
°F (1.1 to 5.5 °C). The default value is 5 °F (2.8 °C).
Only visible if the Indoor Unit supports heat or an
auxiliary heat source is congured.
System Settings
The System Settings let you congure general
heat pump settings.
Min Cycle O Time Sets the minimum
equipment o time between cycles: 240 to
900 seconds (default is 240 seconds).
Min Cycle On Time Sets the minimum
equipment run time in cool mode: 1 to 20
min (default is 3 min).
Min Outdoor Temp Disables the compressor
when the outside air temperature reaches
the congured minimum setting. This
performs two functions. It prevents the
compressor from running when the outdoor
temperature is too low, thus resulting in
To congure the
system settings:
From the Home screen,
press MENU.
Select Settings
Installation Settings.
Congure the devices
connected to the
thermostat.