Daikin FDKS25CVMB Service Manual

Browse online or download Service Manual for Split-system air conditioners Daikin FDKS25CVMB. Daikin FDKS25CVMB Service manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 335
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - Service

SiENBE12-522ASuper Multi NXSerie DService Manual[Applied Models]!Inverter Multi : Cooling Only!Inverter Multi : Heat Pump

Page 2 - D-Series

SiENBE12-522A Introductionix1.1.3 Inspection after RepairBe sure to use an exclusive power circuit for the equipment, and follow the technical standar

Page 3 - !Heat Pump

SiENBE12-522A Main FunctionsFunction and Control 891.7 Night Set ModeWhen the OFF timer is set, the Night Set circuit automatically activates.The Nigh

Page 4 - Function and Control81

Main Functions SiENBE12-522A90 Function and Control1.8 ECONO ModeOutline FTK(X)S20-35D, CTK(X)S50DThe "ECONO mode" reduces the maximum opera

Page 5 - Service Diagnosis197

SiENBE12-522A Main FunctionsFunction and Control 911.9 INTELLIGENT EYEThis is the function that detects existence of humans in the room by a human mot

Page 6 - Table of Contents v

Main Functions SiENBE12-522A92 Function and Control" Since the set temperature is shifted by 2°C higher for 40 minutes, compressor speed becomes

Page 7 - Drawings & Flow Chartsv

SiENBE12-522A Main FunctionsFunction and Control 931.10 HOME LEAVE OperationOutline In order to respond to the customer's need for immediate heat

Page 8 - 1. Introduction

Main Functions SiENBE12-522A94 Function and Control1.11 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to ful

Page 9

SiENBE12-522A Main FunctionsFunction and Control 951.12 Other Functions1.12.1 Hot Start FunctionHeat Pump OnlyIn order to prevent the cold air blast t

Page 10 - 1.1.3 Inspection after Repair

Main Functions SiENBE12-522A96 Function and Control1.12.7 Air Purifying Filter with Photocatalytic Deodorizing FunctionThis filter incorporates the be

Page 11 - 1.1.5 Using Icons List

SiENBE12-522A Function of Main Structural PartsFunction and Control 972. Function of Main Structural Parts2.1 Main Structural PartsHeat Pump ModelCool

Page 12 - List of Functions

Function of Main Structural Parts SiENBE12-522A98 Function and Control2.2 Function of Thermistor2.2.1 Heat Pump ModelA Outdoor Heat Exchanger Thermi

Page 13 - 1. List of Functions

Introduction SiENBE12-522Ax1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is

Page 14 - List of Functions 3

SiENBE12-522A Function of Main Structural PartsFunction and Control 99D Indoor Heat Exchanger Thermistor (DCN)1. The indoor heat exchanger thermisto

Page 15 - 4 List of Functions

Function of Main Structural Parts SiENBE12-522A100 Function and Control2.2.2 Cooling Only ModelA Outdoor Heat Exchanger Thermistor (DCB)1. The outdo

Page 16 - List of Functions 5

SiENBE12-522A Function of Main Structural PartsFunction and Control 101D Indoor Heat Exchanger Thermistor (DCN)1. The indoor heat exchanger thermist

Page 17 - 6 List of Functions

Control Specification SiENBE12-522A102 Function and Control3. Control Specification3.1 Mode HierarchyOutline There are two modes; the mode selected in

Page 18 - List of Functions 7

SiENBE12-522A Control SpecificationFunction and Control 1033.2 Frequency ControlOutline Frequency that corresponds to each room’s capacity will be det

Page 19 - 1.2 Heat Pump Models

Control Specification SiENBE12-522A104 Function and Control2. Determine upper limit frequency$ Set a minimum value as an upper limit frequency among t

Page 20 - List of Functions 9

SiENBE12-522A Control SpecificationFunction and Control 1053.3 Controls at Mode Changing / Start-up3.3.1 Preheating OperationOutline Operate the inver

Page 21 - 10 List of Functions

Control Specification SiENBE12-522A106 Function and Control3.4 Discharge Pipe ControlOutline The discharge pipe temperature is used as the compressor&

Page 22 - List of Functions 11

SiENBE12-522A Control SpecificationFunction and Control 1073.6 Freeze-up Protection ControlOutline During cooling operation, the signals being sent fr

Page 23 - 12 List of Functions

Control Specification SiENBE12-522A108 Function and Control3.8 Fan ControlOutline Fan control is carried out with following functions.1. Fan ON contro

Page 24 - List of Functions 13

SiENBE12-522AList of Functions 1Part 1List of Functions1. List of Functions ...

Page 25 - 14 List of Functions

SiENBE12-522A Control SpecificationFunction and Control 1093.10 Defrost ControlOutline Heat Pump OnlyDefrosting is carried out by the cooling cycle (r

Page 26 - List of Functions 15

Control Specification SiENBE12-522A110 Function and Control3.11 Low Hz High Pressure LimitOutline Heat Pump OnlySet the upper limit of high pressure i

Page 27 - 16 List of Functions

SiENBE12-522A Control SpecificationFunction and Control 111Detail The followings are the examples of control which function in each mode by the electr

Page 28 - List of Functions 17

Control Specification SiENBE12-522A112 Function and Control3.12.1 Fully Closing with Power ONInitialize the electronic expansion valve when turning on

Page 29 - 18 List of Functions

SiENBE12-522A Control SpecificationFunction and Control 1133.12.7 Disconnection of the Discharge Pipe ThermistorOutline Detect a disconnected discharg

Page 30 - Specifications

Control Specification SiENBE12-522A114 Function and Control3.13 Malfunctions3.13.1 Sensor Malfunction DetectionSensor malfunction may occur either in

Page 31 - 1. Specifications

SiENBE12-522A Control SpecificationFunction and Control 115Detail Judgment by Input CurrentWhen an output frequency is exceeds 55 Hz and the input cur

Page 32 - Specifications 21

Control Specification SiENBE12-522A116 Function and Control3.15 Wiring-Error CheckOutline The convenient Wiring Error Check function is designed for t

Page 33 - 22 Specifications

SiENBE12-522A Control SpecificationFunction and Control 117Checking the current setting data on the microcomputer memoryThose data can be checked by l

Page 34 - Specifications 23

Control Specification SiENBE12-522A118 Function and Control3.16 Additional Function3.16.1 Connection Pipe Condensation Preventing FunctionThis control

Page 35 - 24 Specifications

List of Functions SiENBE12-522A2 List of Functions1. List of Functions1.1 Cooling Only ModelsCategory FunctionsFTKS20-35D(2)VMW(L)(9)CTKS50D(2)VMW(L)F

Page 36 - Specifications 25

SiENBE12-522A Control SpecificationFunction and Control 1193.16.5 Cooling / Heating Mode LockUse the S15 connector to set the unit to only cool or hea

Page 37 - 26 Specifications

Control Specification SiENBE12-522A120 Function and Control

Page 38 - Specifications 27

SiENBE12-522ASystem Configuration 121Part 5System Configuration1. System Configuration...

Page 39 - 28 Specifications

System Configuration SiENBE12-522A122 System Configuration1. System Configuration1.1 Operation InstructionsAfter the installation and test operation o

Page 40 - Duct Connected Type

SiENBE12-522A InstructionSystem Configuration 1232. Instruction 2.1 Manual Contents and Reference PageH : Illustrations are for wall mounted type FTXS

Page 41 - 30 Specifications

Instruction SiENBE12-522A124 System Configuration2.2 Safety PrecautionsREAD BEFORE OPERATIONSafety precautions•Keep this manual where the operator can

Page 42 - Specifications 31

SiENBE12-522A InstructionSystem Configuration 125•Do not stand or sit on the outdoor unit. Do not place any object on the unit to avoid injury, do not

Page 43 - 32 Specifications

Instruction SiENBE12-522A126 System Configuration2.3 Names of PartsFTK(X)S20/25/35D, CTK(X)S50DNames of parts"Indoor UnitON/OFF16 141315121345791

Page 44 - Floor Standing Type

SiENBE12-522A InstructionSystem Configuration 127"Outdoor Unit"Indoor Unit1. Air filter2. Titanium Apatite Photocatalytic Air-Purifying Filt

Page 45 - 34 Specifications

Instruction SiENBE12-522A128 System Configuration"Remote Controller1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It di

Page 46 - Specifications 35

SiENBE12-522A List of FunctionsList of Functions 3Category FunctionsFTKS50-71BVMBFDKS25·35CVMBCDKS50·60CVMBCategory FunctionsFTKS50-71BVMBFDKS25·35CVM

Page 47 - 36 Specifications

SiENBE12-522A InstructionSystem Configuration 129FTK(X)S20/25/35C, ATXS20/25/35D, ATXS20/25/35CNames of parts Indoor UnitONOFF13456791011214 15 16812

Page 48 - Specifications 37

Instruction SiENBE12-522A130 System Configuration Outdoor Unit Indoor Unit1. Air filter2.Air purifying filter with photocatalyticdeodorizing functi

Page 49 - 38 Specifications

SiENBE12-522A InstructionSystem Configuration 131 Remote Controller1. Signal transmitter:•It sends signals to the indoor unit.2. Display:• It displays

Page 50 - Specifications 39

Instruction SiENBE12-522A132 System ConfigurationFTK(X)S50/60/71B, ATXS50D, ATXS50CNames of parts Indoor Unit Main unit control panel71411121343151291

Page 51 - 1.3 Indoor Units - Heat Pump

SiENBE12-522A InstructionSystem Configuration 133 Outdoor Unit Indoor Unit1.Air filter2. Air purifying filter with photocatalyticdeodorizing functi

Page 52 - Specifications 41

Instruction SiENBE12-522A134 System Configuration Remote Controller1. Signal transmitter:•It sends signals to the indoor unit.2. Display:•It displays

Page 53 - 42 Specifications

SiENBE12-522A InstructionSystem Configuration 135FDK(X)S25/35C, CDK(X)S50/60C Names of partsIndoor Unit36891071452"

Page 54 - Specifications 43

Instruction SiENBE12-522A136 System Configuration Outdoor Unit Indoor Unit1.Air outlet2. Air outlet grille (Field supply)• Appearance of the Air o

Page 55 - 44 Specifications

SiENBE12-522A InstructionSystem Configuration 137 Remote Controller1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displa

Page 56 - Specifications 45

Instruction SiENBE12-522A138 System ConfigurationFLK(X)S25/35/50/60Names of parts Indoor UnitThe indoor unit can be installed either to the ceiling or

Page 57 - 46 Specifications

List of Functions SiENBE12-522A4 List of FunctionsCategory FunctionsFLKS25-60BVMBFVKS25-50BVMB3MKS50D(2)VMB4MKS58·75D(2)VMB4MKS90DVMBCategory Function

Page 58 - Specifications 47

SiENBE12-522A InstructionSystem Configuration 139 Outdoor Unit Indoor Unit1. Louvres (vertical blades):The louvres are inside of the air outlet.2.

Page 59 - 48 Specifications

Instruction SiENBE12-522A140 System Configuration Remote Controller1. Signal Transmitter:• It sends signals to the indoor unit.2. Display:• It displa

Page 60 - Specifications 49

SiENBE12-522A InstructionSystem Configuration 141FVK(X)S25/35/50Names of parts Indoor Unit Opening the front grilleHow to open the grilleCAUTIONBefore

Page 61 - 50 Specifications

Instruction SiENBE12-522A142 System Configuration Outdoor Unit Indoor Unit1. Photocatalytic deodorizing filter andAir purifying filter:•These filte

Page 62 - Specifications 51

SiENBE12-522A InstructionSystem Configuration 143 Remote Controller1. Signal transmitter:•It sends signals to the indoor unit.2. Display:• It displays

Page 63

Instruction SiENBE12-522A144 System Configuration2.4 Preparation before OperationPreparation Before Operation To set the batteries1. Press with a fi

Page 64 - Specifications 53

SiENBE12-522A InstructionSystem Configuration 145Preparation Before Operation To operate the remote controller• To use the remote controller, aim the

Page 65 - 54 Specifications

Instruction SiENBE12-522A146 System Configuration To set the clock1. Press “CLOCK button”.is displayed.blinks.2. Press “TIMER setting button” to set t

Page 66 - Specifications 55

SiENBE12-522A InstructionSystem Configuration 1472.5 AUTO · DRY · COOL · HEAT · FAN OperationOPERATIONAUTO · DRY · COOL · HEAT · FAN OperationThe air

Page 67 - 56 Specifications

Instruction SiENBE12-522A148 System Configuration To change the air flow rate setting5. Press “FAN setting button”.•Indoor unit quiet operationWhen th

Page 68 - Specifications 57

SiENBE12-522A List of FunctionsList of Functions 5Category FunctionsFTKS20-35DAVMW(L)FTKS20-35D3VMW(L)FTKS20-35CAVMBCategory FunctionsFTKS20-35DAVMW(L

Page 69 - 1.4 Outdoor Units - Heat Pump

SiENBE12-522A InstructionSystem Configuration 1492.6 Adjusting the Air Flow DirectionFTK(X)S20/25/35D, CTK(X)S50DAdjusting the Air Flow DirectionYou c

Page 70 - Specifications 59

Instruction SiENBE12-522A150 System Configuration"To start COMFORT AIRFLOW operation3. Press “COMFORT AIRFLOW button”.The flap position will chan

Page 71 - 60 Specifications

SiENBE12-522A InstructionSystem Configuration 151FTK(X)S20/25/35C, ATXS20/25/35D, ATXS20/25/35CAdjusting the Air Flow DirectionYou can adjust the air

Page 72 - Specifications 61

Instruction SiENBE12-522A152 System Configuration To adjust the vertical blades (louvers)Hold the knob and move the louvers.(You will find a knob on t

Page 73 - 62 Specifications

SiENBE12-522A InstructionSystem Configuration 153FTK(X)S50/60/71B, ATXS50D, ATXS50CAdjusting the Air Flow DirectionYou can adjust the air flow directi

Page 74 - Specifications 63

Instruction SiENBE12-522A154 System Configuration" To 3-D Airflow1. 3. Press the “SWING button ” and the “SWING button ”:the “ ” and “ ” displa

Page 75 - 64 Specifications

SiENBE12-522A InstructionSystem Configuration 155FLK(X)S25/35/50/60Adjusting the Air Flow DirectionYou can adjust the air flow direction to increase y

Page 76 - Connector Wiring Diagram

Instruction SiENBE12-522A156 System Configuration To adjust the vertical blades (louvres)• When adjusting the louvre, use a robust and stable stool a

Page 77 - 1.1 Wall Mounted Type

SiENBE12-522A InstructionSystem Configuration 157FVK(X)S25/35/50Adjusting the Air Flow DirectionYou can adjust the air flow direction to increase your

Page 78 - PCB(1): Control PCB

Instruction SiENBE12-522A158 System Configuration Air flow selection•Make air flow selection according to what suits you.When setting the air flow sel

Page 79 - Connectors

List of Functions SiENBE12-522A6 List of FunctionsCategory FunctionsFTKS71BAVMBFDKS25·35CAVMBCategory FunctionsFTKS71BAVMBFDKS25·35CAVMBBasic Function

Page 80

SiENBE12-522A InstructionSystem Configuration 1592.7 POWERFUL OperationPOWERFUL OperationPOWERFUL operation quickly maximizes the cooling (heating) ef

Page 81 - PCB(2): Signal Receiver PCB

Instruction SiENBE12-522A160 System Configuration2.8 OUTDOOR UNIT SILENT OperationOUTDOOR UNIT SILENT OperationOUTDOOR UNIT SILENT operation lowers t

Page 82

SiENBE12-522A InstructionSystem Configuration 1612.9 ECONO OperationECONO OperationECONO operation is a function which enables efficient operation by

Page 83

Instruction SiENBE12-522A162 System Configuration2.10 HOME LEAVE OperationHOME LEAVE OperationHOME LEAVE operation is a function which allows you to r

Page 84 - 1.2 Duct Connected Type

SiENBE12-522A InstructionSystem Configuration 163 What’s the HOME LEAVE operationIs there a set temperature and air flow rate which is most comfortabl

Page 85 - PCB (2): Display PCB

Instruction SiENBE12-522A164 System Configuration2.11 INTELLIGENT EYE OperationFTK(X)S20/25/35D, CTK(X)S50DINTELLIGENT EYE Operation“INTELLIGENT EYE”

Page 86

SiENBE12-522A InstructionSystem Configuration 165INTELLIGENT EYE Operation“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTI

Page 87 - PCB (4): Signal Receiver PCB

Instruction SiENBE12-522A166 System ConfigurationFTK(X)S20/25/35C, ATXS20/25/35D, ATXS20/25/35CINTELLIGENT EYE Operation“INTELLIGENT EYE” is the infra

Page 88 - 1.4 Floor Standing Type

SiENBE12-522A InstructionSystem Configuration 167 To adjust the angle of the INTELLIGENT EYE sensor• You can adjust the angle of the INTELLIGENT EYE s

Page 89

Instruction SiENBE12-522A168 System ConfigurationFTK(X)S50/60/71B, ATXS50D, ATXS50CINTELLIGENT EYE Operation“INTELLIGENT EYE” is the infrared sensor w

Page 90 - PCB (2): Control PCB

SiENBE12-522A List of FunctionsList of Functions 7Category FunctionsFLKS25-60BAVMBFVKS25-50BAVMB4MKS75D3VMB4MKS90DAVMBCategory FunctionsFLKS25-60BAVMB

Page 91 - 1.5 Outdoor Units

SiENBE12-522A InstructionSystem Configuration 169“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTION###"Energy saving

Page 92 - Function and Control

Instruction SiENBE12-522A170 System Configuration2.12 TIMER OperationTIMER OperationTimer functions are useful for automatically switching the air con

Page 93 - 1. Main Functions

SiENBE12-522A InstructionSystem Configuration 171 To use ON TIMER operation• Check that the clock is correct. If not, set the clock to the present tim

Page 94 - Heating Operation

Instruction SiENBE12-522A172 System Configuration2.13 Note for Multi SystemNote for Multi System〈〈 What is a “Multi System”? 〉〉This system has one out

Page 95 - Auto-Swing

SiENBE12-522A InstructionSystem Configuration 173 Priority Room SettingThe Priority Room Setting requires initial programming during installation. Ple

Page 96 - (R2818) (R2818)

Instruction SiENBE12-522A174 System Configuration2.14 Care and CleaningFTK(X)S20/25/35D, CTK(X)S50DCare and CleaningCAUTION Indoor unit, Outdoor unit

Page 97 - 1.4 Programme Dry Function

SiENBE12-522A InstructionSystem Configuration 1751. Open the front panel. 2. Pull out the air filters.•Push a little upwards the tab at the center of

Page 98 - 1.5 Automatic Operation

Instruction SiENBE12-522A176 System ConfigurationNOTECheck Before a long idle period1. Operate the “FAN only” for several hours on a fine day to dry o

Page 99 - 1.6 Thermostat Control

SiENBE12-522A InstructionSystem Configuration 177FTK(X)S20/25/35C, ATXS20/25/35D, ATXS20/25/35CCARECare and CleaningCAUTION Indoor unit, Outdoor uni

Page 100 - 1.7 Night Set Mode

Instruction SiENBE12-522A178 System Configuration1. Open the front grille. 2. Pull out the air filters.•Push a little upwards the tab at the center of

Page 101 - 1.8 ECONO Mode

List of Functions SiENBE12-522A8 List of Functions1.2 Heat Pump ModelsCategory FunctionsFTXS20-35D(2)VMW(L)(9)CTXS50D(2)VMW(L)FTXS20-35CVMB(9)(8)Categ

Page 102 - 1.9 INTELLIGENT EYE

SiENBE12-522A InstructionSystem Configuration 179 Before a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out the in

Page 103 - 92 Function and Control

Instruction SiENBE12-522A180 System ConfigurationFTK(X)S50/60/71B, ATXS50D, ATXS50CCARECare and CleaningCAUTION" Indoor unit, Outdoor unit and Re

Page 104 - 1.10 HOME LEAVE Operation

SiENBE12-522A InstructionSystem Configuration 1811. Open the front grille. 2. Pull out the air filters.•Push a little upwards the tab at the center of

Page 105 - Details of the

Instruction SiENBE12-522A182 System Configuration Check" Before a long idle period1. Operate the “FAN only” for several hours on a fine day to dr

Page 106 - ON/OFF button

SiENBE12-522A InstructionSystem Configuration 183FDK(X)S25/35C, CDK(X)S50/60CCARECare and CleaningCAUTION "Cleaning the air filter.1.Removing th

Page 107 - 1.12.10Auto-restart Function

Instruction SiENBE12-522A184 System Configuration"Cleaning the drain pan•Clean the drain pan periodically, or drain piping may be clogged with du

Page 108 - 2.1 Main Structural Parts

SiENBE12-522A InstructionSystem Configuration 185FLK(X)S25/35/50/60Care and CleaningCAUTION Indoor unit, Outdoor unit and Remote controller1. Wipe t

Page 109 - 2.2 Function of Thermistor

Instruction SiENBE12-522A186 System Configuration1. Open the front grille.2. Pull out the air filters.• Push upwards the tab at the center of each air

Page 110 - Thermistor (DLN)

SiENBE12-522A InstructionSystem Configuration 187Check"Before a long idle period1. Operate the “FAN only” for several hours on a fine day to dry

Page 111 - 2.2.2 Cooling Only Model

Instruction SiENBE12-522A188 System ConfigurationFVK(X)S25/35/50Care and CleaningCAUTION Indoor unit, Outdoor unit and Remote controller1. Wipe them

Page 112

SiENBE12-522ATable of Contents iSUPER MULTI NXD-Series!Cooling OnlyIndoor UnitFTKS20D(2)VMW(L)(9) FTKS20CVMB(9) FDKS25CVMB FLKS25BVMBFTKS25D(2)VMW(L)(

Page 113 - 3. Control Specification

SiENBE12-522A List of FunctionsList of Functions 9Category FunctionsFTXS50-71BVMBFDXS25·35CVMBCDXS50·60CVMBCategory FunctionsFTXS50-71BVMBFDXS25·35CVM

Page 114 - 3.2 Frequency Control

SiENBE12-522A InstructionSystem Configuration 1891. Open the front grille.2. Remove the air filter.•Press the claws on the right and left of the air f

Page 115

Instruction SiENBE12-522A190 System ConfigurationCheck"Before a long idle period1. Operate the “FAN only” for several hours on a fine day to dry

Page 116 - 3.3.4 3 Minutes Stand-by

SiENBE12-522A InstructionSystem Configuration 1912.15 Troubleshooting TROUBLE SHOOTINGTrouble ShootingThe following cases are not air conditioner trou

Page 117 - 3.5 Input Current Control

Instruction SiENBE12-522A192 System ConfigurationPlease check again before calling a repair person.Check again.Case CheckThe air conditioner does not

Page 118 - 3.7 Heating Peak-cut Control

SiENBE12-522A InstructionSystem Configuration 193WARNING When an abnormality (such as a burning smell) occurs, stop operation and turn the breaker OF

Page 119 - 3.8 Fan Control

Instruction SiENBE12-522A194 System ConfigurationFAULT DIAGNOSIS BY REMOTE CONTROLLERIn the ARC433A series, the temperature display sections on the ma

Page 120 - 3.10 Defrost Control

SiENBE12-522A InstructionSystem Configuration 195LED ON OUTDOOR UNIT PCB 3MXS, 3MKS, 4MXS, 4MKS seriesLED ON OUTDOOR UNIT PCB 2MXS, 2MKS ser

Page 121 - Detail Separate into Zones

Instruction SiENBE12-522A196 System Configuration

Page 122 - Function and Control 111

SiENBE12-522AService Diagnosis 197Part 6Service Diagnosis1. Caution for Diagnosis...

Page 123

Caution for Diagnosis SiENBE12-522A198 Service Diagnosis1. Caution for Diagnosis1.1 Troubleshooting with Operation LampThe operation lamp flashes when

Page 124 - 3.12.10 Oil Recovery Function

List of Functions SiENBE12-522A10 List of FunctionsCategory FunctionsFLXS25-60BVMBFVXS25-50BVMBCategory FunctionsFLXS25-60BVMBFVXS25-50BVMBBasic Funct

Page 125 - Gas insufficient

SiENBE12-522A Caution for DiagnosisService Diagnosis 199Caution: Operation stops suddenly. (Operation lamp blinks.)Cause of above trouble could be &qu

Page 126 - 3.14 Forced Operation Mode

Problem Symptoms and Measures SiENBE12-522A200 Service Diagnosis2. Problem Symptoms and MeasuresProblem Symptom Check Item Details of Measure Page No.

Page 127 - 3.15 Wiring-Error Check

SiENBE12-522A Service Check FunctionService Diagnosis 2013. Service Check FunctionIn the ARC433A series remote controller, the temperature display sec

Page 128 - Function and Control 117

Service Check Function SiENBE12-522A202 Service DiagnosisCheck Method 21. Enter the diagnosis mode.Press the 3 buttons (TEMPs,TEMPt, MODE) simultaneou

Page 129 - 3.16 Additional Function

SiENBE12-522A Service Check FunctionService Diagnosis 2035. Press the TEMP button.Press TEMPs or TEMPt and change the digit until you hear the sound o

Page 130 - 5<C>3<H>1

Code Indication on the Remote Controller SiENBE12-522A204 Service Diagnosis4. Code Indication on the Remote Controller4.1 Error Codes and Description

Page 131 - 120 Function and Control

SiENBE12-522A TroubleshootingService Diagnosis 2055. Troubleshooting5.1 Indoor Units - : Not used for troubleshooting ∗ : Varies depending on the case

Page 132 - System Configuration

Troubleshooting SiENBE12-522A206 Service Diagnosis5.2 Outdoor Units4: ON, 1: OFF, 5: BlinksGreen : Flashes when in normal conditionRed : OFF in normal

Page 133 - 1. System Configuration

SiENBE12-522A TroubleshootingService Diagnosis 2075.3 Indoor Unit PCB AbnormalityRemote Controller DisplayA1Method of Malfunction DetectionEvaluation

Page 134 - 2. Instruction

Troubleshooting SiENBE12-522A208 Service Diagnosis5.4 Freeze-up Protection Control or High Pressure ControlRemote Controller DisplayA5Method of Malfun

Page 135 - Safety precautions

SiENBE12-522A List of FunctionsList of Functions 11Category Functions2MXS52D(2)VMB3MXS52D(2)VMB4MXS68D(2)VMB4MXS80DVMBCategory Functions2MXS52D(2)VMB3

Page 136 - System relocation

SiENBE12-522A TroubleshootingService Diagnosis 209TroubleshootingCheck No.06Refer to P.247Note: If the outside temperature is below –10°C in the cooli

Page 137 - Indoor Unit

Troubleshooting SiENBE12-522A210 Service Diagnosis5.5 Fan Motor or Related Abnormality5.5.1 AC MotorRemote Controller DisplayA6Method of Malfunction D

Page 138 - Outdoor Unit

SiENBE12-522A TroubleshootingService Diagnosis 2115.5.2 DC MotorRemote Controller DisplayA6Method of Malfunction DetectionThe rotation speed detected

Page 139 - Remote Controller

Troubleshooting SiENBE12-522A212 Service DiagnosisTroubleshootingCheck No.01Refer to P.244Check No.02Refer to P.244Replace fan motor.Replace indoor un

Page 140

SiENBE12-522A TroubleshootingService Diagnosis 2135.6 Thermistor or Related Abnormality (Indoor Unit)Remote Controller DisplayC4, C9 Method of Malfunc

Page 141

Troubleshooting SiENBE12-522A214 Service Diagnosis5.7 Shutter Drive Motor / Shutter Limit Switch AbnormalityRemote Controller DisplayC7Method of Malfu

Page 142

SiENBE12-522A TroubleshootingService Diagnosis 2155.8 Signal Transmission Error (between Indoor and Outdoor Units)Remote Controller DisplayU4Method of

Page 143

Troubleshooting SiENBE12-522A216 Service Diagnosis5.9 Unspecified Voltage (between Indoor and Outdoor Units)Remote Controller Display UAMethod of Malf

Page 144

SiENBE12-522A TroubleshootingService Diagnosis 2175.10 Freeze-up Protection ControlRemote Controller DisplayA5Outdoor Unit LED DisplayA 5 1 4 2 1

Page 145

Troubleshooting SiENBE12-522A218 Service DiagnosisTroubleshootingCheck No.04Refer to P.245Check No.06Refer to P.247Check the wiring and piping.Check N

Page 146

List of Functions SiENBE12-522A12 List of FunctionsCategory FunctionsATXS20-35DVMBATXS20-35CVMB(9)Category FunctionsATXS20-35DVMBATXS20-35CVMB(9)Basic

Page 147 - ■ Outdoor Unit

SiENBE12-522A TroubleshootingService Diagnosis 2195.11 OL Activation (Compressor Overload)Remote Controller DisplayE5Outdoor Unit LED DisplayA 5 1 4

Page 148 - ■ Remote Controller

Troubleshooting SiENBE12-522A220 Service Diagnosis5.12 Compressor LockRemote Controller DisplayE6Outdoor Unit LED DisplayA 5 1 1 2 4 3 4 4 1Me

Page 149

SiENBE12-522A TroubleshootingService Diagnosis 2215.13 DC Fan LockRemote Controller DisplayE7Outdoor Unit LED DisplayA 5 1 4 2 4 3 4 4 4Method

Page 150

Troubleshooting SiENBE12-522A222 Service Diagnosis5.14 Input Over Current DetectionRemote Controller DisplayE8Outdoor Unit LED DisplayA 5 1 1 2 4

Page 151

SiENBE12-522A TroubleshootingService Diagnosis 223TroubleshootingCheck No.07Refer to P.248Check No.08Refer to P.249Check No.14Refer to P.252Replace th

Page 152

Troubleshooting SiENBE12-522A224 Service Diagnosis5.15 Four Way Valve AbnormalityRemote Controller DisplayEAOutdoor Unit LED DisplayA 5 1 4 2 1

Page 153

SiENBE12-522A TroubleshootingService Diagnosis 225TroubleshootingCheck No.05Refer to P.246Check No.06Refer to P.247Check No.11Refer to P.250Correct.Re

Page 154

Troubleshooting SiENBE12-522A226 Service Diagnosis5.16 Discharge Pipe Temperature ControlRemote Controller DisplayF3Outdoor Unit LED DisplayA 5 1 4

Page 155 - Preparation Before Operation

SiENBE12-522A TroubleshootingService Diagnosis 2275.17 High Pressure Control in CoolingRemote Controller DisplayF6Outdoor Unit LED DisplayA 5 1 4

Page 156

Troubleshooting SiENBE12-522A228 Service DiagnosisTroubleshootingCheck No.04Refer to P.245Check No.06Refer to P.247Check No.07Refer to P.248Check No.0

Page 157 - Turn the breaker ON

SiENBE12-522A List of FunctionsList of Functions 13Category FunctionsATXS50DVMBCategory FunctionsATXS50DVMBBasic FunctionInverter (with Inverter Power

Page 158 - 2. Press “ON/OFF button”

SiENBE12-522A TroubleshootingService Diagnosis 2295.18 Position Sensor AbnormalityRemote Controller DisplayH6Outdoor Unit LED DisplayA 5 1 4 2 4

Page 159 - 148 System Configuration

Troubleshooting SiENBE12-522A230 Service Diagnosis5.19 CT or Related AbnormalityRemote Controller DisplayH8Outdoor Unit LED DisplayA 5 1 4 2 4 3

Page 160 - 1. Press “SWING button”

SiENBE12-522A TroubleshootingService Diagnosis 231TroubleshootingCheck No.12Refer to P.251Turn off the power and turn it on again.Check No. 12Check th

Page 161 - 150 System Configuration

Troubleshooting SiENBE12-522A232 Service Diagnosis5.20 Thermistor or Related Abnormality (Outdoor Unit)Remote Controller DisplayP4, J3, J6, J8, J9, H9

Page 162 - To adjust the horizontal

SiENBE12-522A TroubleshootingService Diagnosis 233TroubleshootingCheck No.06Refer to P.247P4 : Radiation fin thermistorJ3 : Discharge pipe thermistorJ

Page 163 - (louvers)

Troubleshooting SiENBE12-522A234 Service Diagnosis5.21 Electrical Box Temperature RiseRemote Controller DisplayL3Outdoor Unit LED DisplayA 5 1 4 2

Page 164 - System Configuration 153

SiENBE12-522A TroubleshootingService Diagnosis 235TroubleshootingCheck No.06Refer to P.247Check No.07Refer to P.248Check No.09Refer to P.249Turn off t

Page 165 - " To cancel 3-D Airflow

Troubleshooting SiENBE12-522A236 Service Diagnosis5.22 Radiation Fin Temperature RiseRemote Controller DisplayL4Outdoor Unit LED DisplayA 5 1 1 2

Page 166

SiENBE12-522A TroubleshootingService Diagnosis 237TroubleshootingCheck No.06Refer to P.247Check No.07Refer to P.248Check No.09Refer to P.249Turn off t

Page 167 - (louvres)

Troubleshooting SiENBE12-522A238 Service Diagnosis5.23 Output Over Current DetectionRemote Controller DisplayL5Outdoor Unit LED DisplayA 5 1 1 2 1

Page 168

List of Functions SiENBE12-522A14 List of FunctionsCategory FunctionsATXS50CVMB2AMX52D(2)VMB3AMX52C(2)VMBCategory FunctionsATXS50CVMB2AMX52D(2)VMB3AMX

Page 169 - Air flow selection

SiENBE12-522A TroubleshootingService Diagnosis 239TroubleshootingCheck No.07Refer to P.248Check No.08Refer to P.249Check No.13Refer to P.251Fully open

Page 170 - POWERFUL Operation

Troubleshooting SiENBE12-522A240 Service Diagnosis5.24 Insufficient GasRemote Controller DisplayU0Outdoor Unit LED DisplayA 5 1 1 2 1 3 4 4 4M

Page 171 - 1. Press “SILENT button”

SiENBE12-522A TroubleshootingService Diagnosis 241TroubleshootingCheck No.04Refer to P.245Check No.06Refer to P.247Reconnect in position.Open the stop

Page 172 - ECONO Operation

Troubleshooting SiENBE12-522A242 Service Diagnosis5.25 Low-voltage DetectionRemote Controller DisplayU2Outdoor Unit LED DisplayA 5 1 4 2 1 3 1

Page 173 - HOME LEAVE Operation

SiENBE12-522A TroubleshootingService Diagnosis 2435.26 Anti-icing Function in Other Rooms / Unspecified Voltage (between Indoor and Outdoor Units)Remo

Page 174 - Useful in these cases

Check SiENBE12-522A244 Service Diagnosis6. Check6.1 How to Check6.1.1 Fan Motor Connector Output CheckCheck No.01 1. Check connector connection.2. Che

Page 175 - INTELLIGENT EYE Operation

SiENBE12-522A CheckService Diagnosis 2456.1.3 Electronic Expansion Valve CheckCheck No.04 Conduct the followings to check the electronic expansion val

Page 176

Check SiENBE12-522A246 Service Diagnosis6.1.4 Four Way Valve Performance CheckCheck No.05Turn off the power and turn it on again.Start the heating-mod

Page 177

SiENBE12-522A CheckService Diagnosis 2476.1.5 Thermistor Resistance CheckCheck No.06 Remove the connectors of the thermistors on the PCB, and measure

Page 178 - INTELLIGENT EYE

Check SiENBE12-522A248 Service Diagnosis6.1.6 Installation Condition CheckCheck No.07Installation condition checkNormalChange the position of the air

Page 179

SiENBE12-522A List of FunctionsList of Functions 15Category FunctionsFTXS20-35DAVMW(L)FTXS20-35D3VMW(L)FTXS20-35CAVMBCategory FunctionsFTXS20-35DAVMW(

Page 180 - Notes on “INTELLIGENT EYE”

SiENBE12-522A CheckService Diagnosis 2496.1.7 Discharge Pressure CheckCheck No.086.1.8 Outdoor Unit Fan System Check (With DC Motor)Check No.09Dischar

Page 181 - TIMER Operation

Check SiENBE12-522A250 Service Diagnosis6.1.9 Power Supply Waveforms CheckCheck No.10 Measure the power supply waveform between pins 1 and 3 on the te

Page 182 - ATTENTION

SiENBE12-522A CheckService Diagnosis 2516.1.11 Capacitor Voltage CheckCheck No.12 Before this checking, be sure to check the main circuit for short-ci

Page 183 - Note for Multi System

Check SiENBE12-522A252 Service Diagnosis6.1.13 Main Circuit Electrolytic Capacitor CheckCheck No.14 " Checking the main circuit electrolytic capa

Page 184 - Priority Room Setting

SiENBE12-522A CheckService Diagnosis 2536.1.15 Hall IC CheckCheck No.16 1. Check the connector connection.2. With the power ON, operation OFF, and the

Page 185 - Care and Cleaning

Check SiENBE12-522A254 Service Diagnosis

Page 186 - [ Replacement]

SiENBE12-522ARemoval Procedure 255Part 7Removal Procedure1. Outdoor Unit (80 / 90 Class) ...

Page 187 - Before a long idle period

Outdoor Unit (80 / 90 Class) SiENBE12-522A256 Removal Procedure1. Outdoor Unit (80 / 90 Class)1.1 Removal of Outer PanelsProcedure Warning Be sure to

Page 188

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2573Unscrew 3 screws of the right panel, slide it downwards and release the tabs to remov

Page 189

Outdoor Unit (80 / 90 Class) SiENBE12-522A258 Removal Procedure6Unscrew 3 screws of the front panel to remove.7Remove 4 screws of the discharge outlet

Page 190

List of Functions SiENBE12-522A16 List of FunctionsCategory FunctionsFTXS71BAVMBFDXS25·35CAVMBCategory FunctionsFTXS71BAVMBFDXS25·35CAVMBBasic Functio

Page 191

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2591.2 Removal of Propeller FansProcedure Warning Be sure to wait 10 minutes or more after

Page 192 - System Configuration 181

Outdoor Unit (80 / 90 Class) SiENBE12-522A260 Removal Procedure1.3 Removal of Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after

Page 193 - 182 System Configuration

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2613Remove the earth wire.4Remove 1 screw of the terminal board.5Release the tab on the to

Page 194

Outdoor Unit (80 / 90 Class) SiENBE12-522A262 Removal Procedure2. Remove each wire harness1Disconnect 4 connectors of the electronic expansion valve l

Page 195 - Cleaning the drain pan

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2634Remove the connector S92 for gas pipe thermistor.5Remove the connector S90 for thermis

Page 196

Outdoor Unit (80 / 90 Class) SiENBE12-522A264 Removal Procedure8Remove the relay connector for compressor.9Remove the electrical box cover.10Disconnec

Page 197 - Air purifying filter

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 26512Take off the thermistor presser spring, and remove the thermistor." Place the th

Page 198

Outdoor Unit (80 / 90 Class) SiENBE12-522A266 Removal Procedure3Remove the outdoor air thermistor lead wire from the groove.4Remove each wire harness,

Page 199

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2671.4 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning of

Page 200

Outdoor Unit (80 / 90 Class) SiENBE12-522A268 Removal Procedure4Lift the PCB at the terminal board side.5Disconnect each wire harness connector linked

Page 201

SiENBE12-522A List of FunctionsList of Functions 17Category FunctionsFLXS25-60BAVMBFVXS25-50BAVMB4MXS68D3VMB4MXS80DAVMBCategory FunctionsFLXS25-60BAVM

Page 202 - Trouble Shooting

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2696The figure shows the controller PCB.S20: Electronic expansion valve coil A portS21: El

Page 203 - Case Check

Outdoor Unit (80 / 90 Class) SiENBE12-522A270 Removal Procedure1.5 Removal of Fan MotorProcedure Warning Be sure to wait 10 minutes or more after turn

Page 204 - Disposal requirements

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2714Remove 4 screws of the fan motor." When reassembling, fix the lead wire to avoid

Page 205 - Fault diagnosis

Outdoor Unit (80 / 90 Class) SiENBE12-522A272 Removal Procedure1.6 Removal of Electronic Expansion Valve and ThermistorProcedure Warning Be sure to wa

Page 206 - System Configuration 195

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2731.7 Removal of Sound Blanket and ReactorProcedure Warning Be sure to wait 10 minutes or

Page 207 - 196 System Configuration

Outdoor Unit (80 / 90 Class) SiENBE12-522A274 Removal Procedure4Remove the sound blanket (top)." Carefully remove the sound blanket, which is eas

Page 208 - Service Diagnosis

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 2751.8 Removal of ShuntProcedure Warning Be sure to wait 10 minutes or more after turning

Page 209 - 1. Caution for Diagnosis

Outdoor Unit (80 / 90 Class) SiENBE12-522A276 Removal Procedure1.9 Removal of Solenoid Valve and Four Way ValveProcedure Warning Be sure to wait 10 mi

Page 210 - Indication

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 277" Before taking this procedure, make sure there is no refrigerant gas left in the

Page 211

Outdoor Unit (80 / 90 Class) SiENBE12-522A278 Removal Procedure1.10 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or more after tu

Page 212 - 3. Service Check Function

List of Functions SiENBE12-522A18 List of FunctionsCategory FunctionsATXS20-35DAVMBCategory FunctionsATXS20-35DAVMBBasic FunctionInverter (with Invert

Page 213 - → See 7.)

SiENBE12-522A Outdoor Unit (80 / 90 Class)Removal Procedure 279" Make sure there is no refrigerant gas left inside the refrigerant pipes before s

Page 214 - → Refer to page 204.)

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A280 Removal Procedure2. Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)2.1 Removal of Outer Panel

Page 215

SiENBE12-522A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)Removal Procedure 2812.2 Removal of Electrical BOXProcedure Warning Be sure to wait 10 minute

Page 216 - 5. Troubleshooting

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A282 Removal Procedure3Pull out the terminal board to open." Glass tube fuse and varistor

Page 217 - 5.2 Outdoor Units

SiENBE12-522A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)Removal Procedure 2834Disconnect the compressor relay connector.5Remove the reactor lead wire

Page 218

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A284 Removal Procedure2Remove 1 screw of the electrical box.3Remove the drip-proof cover.4Disc

Page 219 - 208 Service Diagnosis

SiENBE12-522A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)Removal Procedure 2852.3 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more a

Page 220

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A286 Removal Procedure5Lift up the control PCB.6Disconnect each wire harness connector linked

Page 221 - 5.5.1 AC Motor

SiENBE12-522A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)Removal Procedure 2877The figure shows the control PCB." Glass tube fuse 3A2. Removing t

Page 222 - 5.5.2 DC Motor

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A288 Removal Procedure2.4 Removal of Fan MotorProcedure Warning Be sure to wait 10 minutes or

Page 223

SiENBE12-522Aii Table of Contents!Heat PumpIndoor UnitFTXS20D(2)VMW(L)(9) ATXS20DVMB FDXS25CVMB FLXS25BVMBFTXS25D(2)VMW(L)(9) ATXS25DVMB FDXS35CVMB FL

Page 224 - Service Diagnosis 213

SiENBE12-522ASpecifications 19Part 2Specifications1. Specifications ...

Page 225 - 214 Service Diagnosis

SiENBE12-522A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)Removal Procedure 2892.5 Removal of Sound BlanketProcedure Warning Be sure to wait 10 minutes

Page 226 - Service Diagnosis 215

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A290 Removal Procedure2.6 Removal of Four Way Valve Coil, Solenoid Valve Coil, Electronic Expa

Page 227 - 216 Service Diagnosis

SiENBE12-522A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)Removal Procedure 2915Take off the putty, and remove each thermistor." Place the thermis

Page 228 - 5 1 4 2 1 3 4 4 4

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A292 Removal Procedure2.7 Removal of Four Way Valve, Solenoid Valve and ShuntProcedure Warning

Page 229

SiENBE12-522A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)Removal Procedure 2932.8 Removal of Solenoid Valve and ShuntProcedure Warning Be sure to wait

Page 230 - 5 1 4 2 1 3 4 4 1

Outdoor Unit (50 / 52 / 58 / 68 / 75 Class) SiENBE12-522A294 Removal Procedure2.9 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or

Page 231 - 5.12 Compressor Lock

SiENBE12-522AOthers 295Part 8Others1. Others ...2961.1 T

Page 232 - 5.13 DC Fan Lock

Others SiENBE12-522A296 Others1. Others1.1 Test Run from the Remote ControllerFor Heat pump In cooling mode, select the lowest programmable temperatur

Page 233 - 5 1 1 2 4 3 1 4 4

SiENBE12-522A OthersOthers 2971.2 Jumper Settings1.2.1 When Two Units are Installed in One RoomWhen two indoor units are installed in one room, the tw

Page 234

Others SiENBE12-522A298 Others1.2.3 Adjusting the Angle of the Intelligent Eye SensorFTK(X)S20-35C, ATXS20-35D, ATXS20-35C" Once installation of

Page 235 - 5 1 4 2 1 3 1 4 1

Specifications SiENBE12-522A20 Specifications1. Specifications1.1 Indoor Units - Cooling OnlyWall Mounted Type50Hz 230VModel FTKS20DVMW(9) FTKS20DVMLR

Page 236

SiENBE12-522AAppendix 299Part 9Appendix1. Piping Diagrams...3001.1 Indo

Page 237

Piping Diagrams SiENBE12-522A300 Appendix1. Piping Diagrams1.1 Indoor Units1.1.1 Wall Mounted TypeFTKS20/25/35D(2)VMW(L)(9)FTKS20/25/35DAVMW(L)FTKS20/

Page 238

SiENBE12-522A Piping DiagramsAppendix 301FTKS20/25/35CVMB(9)(8)FTKS20/25/35CAVMBFTXS20/25/35CVMB(9)(8)ATXS20/25/35DVMB, ATXS20/25/35CVMB(9)FTXS20/25/3

Page 239

Piping Diagrams SiENBE12-522A302 AppendixFTXS71BVMB, FTXS71BAVMB1.1.2 Duct Connected TypeFDK(X)S25/35CVMB, CDK(X)S50/60CVMB, FDK(X)S25/35CAVMB(15.9CuT

Page 240 - 5 1 4 2 4 3 1 4 1

SiENBE12-522A Piping DiagramsAppendix 3031.1.3 Floor / Ceiling Suspended Dual TypeFLKS25/35BVMB, FLKS25/35BAVMB FLKS50/60BVMB, FLKS50/60BAVMBFLXS25/3

Page 241

Piping Diagrams SiENBE12-522A304 Appendix1.1.4 Floor Standing TypeFVXS25/35BVMB, FVXS25/35BAVMB FVKS25/35BVMB, FVKS25/35BAVMBFVXS50BVMB, FVXS50BAVMB F

Page 242

SiENBE12-522A Piping DiagramsAppendix 3051.2 Outdoor Units1.2.1 Cooling Only3MKS50DVMB, 3MKS50D2VMB4MKS58DVMB, 4MKS58D2VMBREFRIGERANT FLOW9.5CuTHEAT E

Page 243 - P4, J3, J6, J8, J9, H9

Piping Diagrams SiENBE12-522A306 Appendix4MKS75DVMB, 4MKS75D2VMB, 4MKS75D3VMB4MKS90DVMB, 4MKS90DAVMBREFRIGERANT FLOW9.5CuTHEAT EXCHANGERTHERMISTOR(DE)

Page 244

SiENBE12-522A Piping DiagramsAppendix 3071.2.2 Heat Pump2MXS52DVMB, 2MXS52D2VMB, 2AMX52DVMB, 2AMX52D2VMB3MXS52DVMB, 3MXS52D2VMB, 3AMX52CVMB, 3AMX52C2V

Page 245 - 5 1 4 2 4 3 1 4 4

Piping Diagrams SiENBE12-522A308 Appendix4MXS68DVMB, 4MXS68D2VMB, 4MXS68D3VMB4MXS80DVMB, 4MXS80DAVMBREFRIGERANT FLOWHEADERHEAT EXCHANGERTHERMISTOR(DE)

Page 246

SiENBE12-522A SpecificationsSpecifications 2150Hz 230VModel FTKS25DVMW(9) FTKS25DVMLRated Capacity 2.5kW Class 2.5kW ClassFront Panel Color White Silv

Page 247 - 5 1 1 2 1 3 1 4 4

SiENBE12-522A Wiring DiagramsAppendix 3092. Wiring Diagrams2.1 Indoor Units2.1.1 Wall Mounted TypeFTK(X)S20/25/35D(2)VMW(L)(9), CTK(X)S50D(2)VMW(L), F

Page 248

Wiring Diagrams SiENBE12-522A310 AppendixFTK(X)S50BVMB, ATXS50DVMB, ATXS50CVMBFTK(X)S60/71BVMB, FTK(X)S71BAVMB3D038065GCONTROLLERWIRELESSREMOTEPCB4PCB

Page 249 - 5 1 1 2 1 3 4 4 1

SiENBE12-522A Wiring DiagramsAppendix 3112.1.2 Duct Connected TypeFDK(X)S25/35CVMB, CDK(X)S50/60CVMB, FDK(X)S25/35CAVMB2.1.3 Floor / Ceiling Suspended

Page 250

Wiring Diagrams SiENBE12-522A312 Appendix2.1.4 Floor Standing TypeFVK(X)S25/35/50BVMB, FVK(X)S25/35/50BAVMBCONTROLLERWIRELESSREMOTEindoorH1PS1WS2W(4)S

Page 251 - 5.24 Insufficient Gas

SiENBE12-522A Wiring DiagramsAppendix 3132.2 Outdoor Units2.2.1 Cooling only3MKS50DVMB, 3MKS50D2VMB4MKS58DVMB, 4MKS75DVMB, 4MKS90DVMB, 4MKS58D2VMB, 4M

Page 252

Wiring Diagrams SiENBE12-522A314 Appendix2.2.2 Heat Pump2MXS52DVMB, 2AMX52DVMB, 2MXS52D2VMB, 2AMX52D2VMB3MXS52DVMB, 3AMX52CVMB, 3MXS52D2VMB, 3AMX52C2V

Page 253 - 5.25 Low-voltage Detection

SiENBE12-522A Wiring DiagramsAppendix 3154MXS68DVMB, 4MXS80DVMB, 4MXS68D2VMB, 4MXS68D3VMB, 4MXS80DAVMBROOM AROOM BROOM CROOM DTO INDOOR UNIT3333222211

Page 254 - 5 1 1 2 1 3 1 4 1

Wiring Diagrams SiENBE12-522A316 Appendix

Page 255 - 6. Check

SiENBE12-522AIndex iIndexNumerics3 minutes stand-by...105Aa1 ...

Page 256

SiENBE12-522Aii Indexu0...240u2...

Page 257 - Check No.05

Specifications SiENBE12-522A22 Specifications50Hz 230VModel FTKS35DVMW(9) FTKS35DVMLRated Capacity 3.5kW Class 3.5kW ClassFront Panel Color White Silv

Page 258

SiENBE12-522AIndex iiioverload ...114overload relay...

Page 259 - Check No.07

SiENBE12-522Aiv Indextroubleshooting with the operation lamp ...198turning speed pulse input on the outdoor unit pcb check...

Page 260 - Check No.09

SiENBE12-522ADrawings & Flow Charts vDrawings & Flow ChartsAanti-icing function in other rooms ...243arc433a ...

Page 261 - Check No.11

SiENBE12-522Avi Drawings & Flow Charts4mks75d3vmb ...3064mks75dvmb ...

Page 262 - 6.1.12 Power Transistor Check

SiENBE12-522ADrawings & Flow Charts viiftk(x)s20/25/35d(2)vmw(l)(9)...309ftk(x)s20/25/35d3vmw(l) ...

Page 263 - 252 Service Diagnosis

ÉSiENBE12-522ATËÍISO14001 assures an effective environmentalmanagement system in order to help protecthuman health and the environment from thepotenti

Page 264 - 6.1.15 Hall IC Check

SiENBE12-522A SpecificationsSpecifications 2350Hz 230VModel CTKS50D(2)VMW CTKS50D(2)VMLRated Capacity 5.0kW Class 5.0kW ClassFront Panel Color White S

Page 265 - 254 Service Diagnosis

Specifications SiENBE12-522A24 Specifications50Hz 230VModel FTKS35CVMB(9)(8) FTKS50BVMBRated Capacity 3.5kW Class 5.0kW ClassFront Panel Color White W

Page 266 - Removal Procedure

SiENBE12-522A SpecificationsSpecifications 2550Hz 230VModel FTKS20DAVMW FTKS20DAVMLRated Capacity 2.0kW Class 2.0kW ClassFront Panel Color White Silve

Page 267 - 1.1 Removal of Outer Panels

Specifications SiENBE12-522A26 Specifications50Hz 230VModel FTKS25DAVMW FTKS25DAVMLRated Capacity 2.5kW Class 2.5kW ClassFront Panel Color White Silve

Page 268

SiENBE12-522A SpecificationsSpecifications 2750Hz 230VModel FTKS35DAVMW FTKS35DAVMLRated Capacity 3.5kW Class 3.5kW ClassFront Panel Color White Silve

Page 269

Specifications SiENBE12-522A28 Specifications50Hz 230VModel FTKS20CAVMB FTKS25CAVMBRated Capacity 2.0kW Class 2.5kW ClassFront Panel Color White White

Page 270 - 1.2 Removal of Propeller Fans

SiENBE12-522ATable of Contents iii1.3 Indoor Units - Heat Pump...401.4 Outdoor Uni

Page 271 - 1.3 Removal of Electrical Box

SiENBE12-522A SpecificationsSpecifications 29Duct Connected Type50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the e

Page 272

Specifications SiENBE12-522A30 Specifications50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the external static pres

Page 273

SiENBE12-522A SpecificationsSpecifications 31Floor / Ceiling Suspended Dual Type50Hz 230VModel FLKS25BVMB FLKS35BVMBRated Capacity 2.5kW Class 3.5kW C

Page 274

Specifications SiENBE12-522A32 SpecificationsPower Factor % 94.6 94.2Temperature Control Microcomputer Control Microcomputer ControlDimensions (H×W×D)

Page 275

SiENBE12-522A SpecificationsSpecifications 33Floor Standing Type50Hz 230VModel FVKS25BVMB FVKS35BVMBRated Capacity 2.5kW Class 3.5kW ClassFront Panel

Page 276

Specifications SiENBE12-522A34 SpecificationsPower Consumption (Rated) W 32 32Power Factor % 99.4 99.4Temperature Control Microcomputer Control Microc

Page 277 - Procedure Points

SiENBE12-522A SpecificationsSpecifications 351.2 Outdoor Units - Cooling Only50Hz 230VNote:1. The data are based on the conditions shown in the table

Page 278 - 1.4 Removal of PCB

Specifications SiENBE12-522A36 Specifications50Hz 230VNote:1. The data are based on the conditions shown in the table below.Model 4MKS75DVMB 4MKS90DVM

Page 279 - 268 Removal Procedure

SiENBE12-522A SpecificationsSpecifications 3750Hz 230VNote:1. The data are based on the conditions shown in the table below.Model 3MKS50D2VMB 4MKS58D2

Page 280

Specifications SiENBE12-522A38 Specifications50Hz 230VNote:1. The data are based on the conditions shown in the table below.Model 4MKS75D2VMBCooling C

Page 281 - 1.5 Removal of Fan Motor

SiENBE12-522Aiv Table of ContentsPart 5System Configuration1211. System Configuration...

Page 282

SiENBE12-522A SpecificationsSpecifications 3950Hz 230VNote:1. The data are based on the conditions shown in the table below.Model 4MKS75D3VMB 4MKS90DA

Page 283

Specifications SiENBE12-522A40 Specifications1.3 Indoor Units - Heat PumpWall Mounted Type50Hz 230VModelFTXS20DVMW(9) FTXS20DVMLCooling Heating Coolin

Page 284

SiENBE12-522A SpecificationsSpecifications 4150Hz 230VModelFTXS25DVMW(9) FTXS25DVMLCooling Heating Cooling HeatingRated Capacity 2.5kW Class 2.5kW Cla

Page 285

Specifications SiENBE12-522A42 Specifications50Hz 230VModelFTXS35DVMW(9) FTXS35DVMLCooling Heating Cooling HeatingRated Capacity 3.5kW Class 3.5kW Cla

Page 286 - 1.8 Removal of Shunt

SiENBE12-522A SpecificationsSpecifications 4350Hz 230VModelCTXS50D(2)VMW CTXS50D(2)VMLCooling Heating Cooling HeatingRated Capacity 5.0kW Class 5.0kW

Page 287

Specifications SiENBE12-522A44 Specifications50Hz 230VModelFTXS35CVMB(9)(8) FTXS50BVMBCooling Heating Cooling HeatingRated Capacity 3.5kW Class 5.0kW

Page 288

SiENBE12-522A SpecificationsSpecifications 4550Hz 230VModelATXS20DVMB ATXS25DVMBCooling Heating Cooling HeatingRated Capacity 2.0kW Class 2.5kW ClassF

Page 289 - 1.10 Removal of Compressor

Specifications SiENBE12-522A46 Specifications50Hz 230VModelATXS20CVMB(9) ATXS25CVMB(9)Cooling Heating Cooling HeatingRated Capacity 2.0kW Class 2.5kW

Page 290

SiENBE12-522A SpecificationsSpecifications 4750Hz 230VModelFTXS20DAVMW FTXS20DAVMLCooling Heating Cooling HeatingRated Capacity 2.0kW Class 2.0kW Clas

Page 291 - 2.1 Removal of Outer Panels

Specifications SiENBE12-522A48 Specifications50Hz 230VModelFTXS25DAVMW FTXS25DAVMLCooling Heating Cooling HeatingRated Capacity 2.5kW Class 2.5kW Clas

Page 292 - 2.2 Removal of Electrical BOX

SiENBE12-522ATable of Contents v5.20 Thermistor or Related Abnormality (Outdoor Unit)...2325.21 Electrical Box Temperature

Page 293

SiENBE12-522A SpecificationsSpecifications 4950Hz 230VModelFTXS35DAVMW FTXS35DAVMLCooling Heating Cooling HeatingRated Capacity 3.5kW Class 3.5kW Clas

Page 294

Specifications SiENBE12-522A50 Specifications50Hz 230VModelFTXS20CAVMB FTXS25CAVMBCooling Heating Cooling HeatingRated Capacity 2.5kW Class 2.5kW Clas

Page 295

SiENBE12-522A SpecificationsSpecifications 5150Hz 230VModelATXS20DAVMB ATXS25DAVMBCooling Heating Cooling HeatingRated Capacity 2.0kW Class 2.5kW Clas

Page 296 - 2.3 Removal of PCB

Specifications SiENBE12-522A52 SpecificationsDuct Connected Type50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the e

Page 297 - 286 Removal Procedure

SiENBE12-522A SpecificationsSpecifications 5350Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the external static pres

Page 298

Specifications SiENBE12-522A54 SpecificationsFloor / Ceiling Suspended Dual Type50Hz 230VModelFLXS25BVMB FLXS35BVMBCooling Heating Cooling HeatingRate

Page 299 - 2.4 Removal of Fan Motor

SiENBE12-522A SpecificationsSpecifications 5550Hz 230VModelFLXS25BAVMB FLXS35BAVMBCooling Heating Cooling HeatingRated Capacity 2.5kW Class 3.5kW Clas

Page 300 - 2.5 Removal of Sound Blanket

Specifications SiENBE12-522A56 SpecificationsFloor Standing Type50Hz 230VModelFVXS25BVMB FVXS35BVMBCooling Heating Cooling HeatingRated Capacity 2.5kW

Page 301

SiENBE12-522A SpecificationsSpecifications 57Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew ProofRunning Current (Rated) A 0.14

Page 302 - Removal Procedure 291

Specifications SiENBE12-522A58 Specifications1.4 Outdoor Units - Heat Pump50Hz 230VNote:1. The data are based on the conditions shown in the table bel

Page 303

SiENBE12-522Avi Table of Contents2. Wiring Diagrams...3092.1 Indoor Uni

Page 304

SiENBE12-522A SpecificationsSpecifications 5950Hz 230VNote:1. The data are based on the conditions shown in the table below.Model4MXS68DVMB 4MXS80DVMB

Page 305 - 2.9 Removal of Compressor

Specifications SiENBE12-522A60 Specifications50Hz 230VNote:1. The data are based on the conditions shown in the table below.Model2AMX52DVMB 3AMX52CVMB

Page 306 - Others 295

SiENBE12-522A SpecificationsSpecifications 6150Hz 230VNote:1. The data are based on the conditions shown in the table below.Model2MXS52D2VMB 3MXS52D2V

Page 307 - 1. Others

Specifications SiENBE12-522A62 Specifications50Hz 230VNote:1. The data are based on the conditions shown in the table below.Model4MXS68D2VMB 2AMX52D2V

Page 308 - 1.2 Jumper Settings

SiENBE12-522A SpecificationsSpecifications 6350Hz 230VNote:1. The data are based on the conditions shown in the table below.Model3AMX52C2VMBCooling He

Page 309 - 298 Others

Specifications SiENBE12-522A64 Specifications50Hz 230VNote:1. The data are based on the conditions shown in the table below.Model4MXS68D3VMB 4MXS80DAV

Page 310 - Appendix

SiENBE12-522APrinted Circuit Board Connector Wiring Diagram 65Part 3Printed Circuit BoardConnector Wiring Diagram1. Printed Circuit Board Connector Wi

Page 311 - 1. Piping Diagrams

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A66 Printed Circuit Board Connector Wiring Diagram1. Printed Circuit Board Connector Wiring

Page 312 - Appendix 301

SiENBE12-522A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 67PCB Detail PCB(1): Control PCBPCB(4): INT

Page 313 - 1.1.2 Duct Connected Type

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A68 Printed Circuit Board Connector Wiring Diagram1.1.2 FTK(X)S20~35C, ATXS20~35D, ATXS20~3

Page 314 - Appendix 303

SiENBE12-522A Introductionvii1. Introduction1.1 Safety CautionsCautions and Warnings" Be sure to read the following safety cautions before conduc

Page 315 - 1.1.4 Floor Standing Type

SiENBE12-522A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 69PCBJP21JBJAJC5VGND12V(R2413)SW7PCB(1) Con

Page 316 - 1.2 Outdoor Units

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A70 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(1): Control PCBPCB(2): Sig

Page 317 - 4MKS90DVMB, 4MKS90DAVMB

SiENBE12-522A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 711.1.3 FTK(X)S50~71B, ATXS50D, ATXS50CConn

Page 318 - 1.2.2 Heat Pump

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A72 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(1): Control PCB (indoor un

Page 319 - 4MXS80DVMB, 4MXS80DAVMB

SiENBE12-522A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 731.2 Duct Connected TypeConnectorsNote: Ot

Page 320 - 2. Wiring Diagrams

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A74 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (2): Display PCBC1C3C2WLU

Page 321 - 310 Appendix

SiENBE12-522A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 751.3 Floor / Ceiling Suspended Dual TypeCo

Page 322 - 2.1.2 Duct Connected Type

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A76 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (2): Power Supply PCBPCB (

Page 323 - 2.1.4 Floor Standing Type

SiENBE12-522A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 771.4 Floor Standing TypeConnectorsNote: Ot

Page 324 - 2.2 Outdoor Units

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A78 Printed Circuit Board Connector Wiring Diagram

Page 325 - 2.2.2 Heat Pump

Introduction SiENBE12-522Aviii1.1.2 Cautions Regarding Products after RepairCautionDo not repair the electrical components with wet hands.Working on t

Page 326 - Appendix 315

SiENBE12-522A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 79PCB Detail PCB (2): Control PCBPCB (3): D

Page 327 - 316 Appendix

Printed Circuit Board Connector Wiring Diagram SiENBE12-522A80 Printed Circuit Board Connector Wiring Diagram1.5 Outdoor UnitsConnectorsNote: Other De

Page 328

SiENBE12-522AFunction and Control 81Part 4Function and Control1. Main Functions...

Page 329

Main Functions SiENBE12-522A82 Function and Control1. Main FunctionsNote: See the list of functions for the functions applicable to different models.1

Page 330 - Index iii

SiENBE12-522A Main FunctionsFunction and Control 83Inverter Features The inverter provides the following features:" The regulating capacity can b

Page 331

Main Functions SiENBE12-522A84 Function and Control1.2 Power-Airflow Dual Flaps, Wide Angle Louvers and Auto-SwingPower-airflow Dual FlapsThe large fl

Page 332 - Drawings & Flow Charts

SiENBE12-522A Main FunctionsFunction and Control 851.3 Fan Speed Control for Indoor UnitsControl Mode The airflow rate can be automatically controlled

Page 333

Main Functions SiENBE12-522A86 Function and Control1.4 Programme Dry FunctionProgramme dry function removes humidity while preventing the room tempera

Page 334

SiENBE12-522A Main FunctionsFunction and Control 871.5 Automatic OperationAutomatic Cooling / Heating Function (Heat Pump Only)When the AUTO mode is s

Page 335 - ÉSiENBE12-522ATËÍ

Main Functions SiENBE12-522A88 Function and Control1.6 Thermostat ControlThermostat control is based on the difference between the room temperature an