CONTROL SYSTEMS
Building Management System
System Configuration
No. Item Model No. Function
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
conditioning systems through LONWORKS
®
communication.
DMS504B514
3
•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
independently.
DAM411B513-1
No. Item Model No. Function
*2 Interface for use in LONWORKS
®
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
conditioning systems through BACnet
®
communication.
DMS502B51
•Additional 64 groups (10 outdoor units) is possible.
Max. 7 iTM plus adaptors can be connected to intelligent Touch Manager.
DCM601A52
*1 Interface for use in BACnet
®
Optional DIII board
KJB411A
•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
independently.
DAM412B51Optional Di board
•8 pairs based on a pair of On/Off input and abnormality input.DEC101A51Di unit2-5
3-2
1-2
1
Electrical box with earth terminal (4 blocks)
DCS601A521-1 •Additional 64 groups (10 outdoor units) is possible.
•Wall embedded switch box.
DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.
intelligent Touch
Controller
DIII-NET plus adaptor
intelligent Touch Controller
Hardware
HardwareBasic
DCM601A51 •Air-conditioning management system that can be controlled by touch screen.
intelligent Touch Manager
DCM601A53 •Max. 5 intelligent Touch Managers can be integrated.iTM integrator
HardwareBasic
Option
iTM plus adaptor
•Building energy consumption is visualised.
Wasted air-conditioning energy can be found out.
DCM008A51iTM energy navigator
•Power consumption of indoor units are calculated based on operation status of the indoor unit and
outdoor unit power consumption measured by kWh metre.
DCM002A51
iTM power proportional
distribution
2
2-2
2-1
2-4
2-3
Hardware
Software
Option
•4 pairs based on a pair of On/Off input and abnormality input.DEC102A51Dio unit2-6
•Interface between the central monitoring board and central control units.DCS302A525
Unification adaptor for
computerised control
Notes: *1.
BACnet
®
is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS
®
is a trademark of Echelon Corporation registered in the United States and other countries.
*3. Installation box for adaptor must be obtained locally.
Communication
line
Contact/analogue
signal
intelligent Touch
Manager
Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
system.
Note 2
DCS302CA61
Central remote controller2
•Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF,
temperature settings and scheduling can be controlled individually for indoor units.
Note 3
DCS303A51
Residential central remote controller1
•Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
Note 2
DCS301BA61
Unified ON/OFF controller3
KJB212AA
Electrical box with earth terminal (2 blocks)3-1
KEK26-1A
Noise filter (for electromagnetic interface use only)3-2
KJB311AA
Electrical box with earth terminal (3 blocks)2-1
DTA102A52
Interface adaptor for SkyAir series
5
DTA107A55
6
DTA103A51
Wiring adaptor for other air-conditioner7
•Up to 1024 units can be centrally controlled in 64 different groups.
•Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16)
apply to each adaptor.
DTA109A51
D -NET
Expander Adaptor
8
•Fixing plate for DTA109A51KRP4A92
Mounting plate
8-1
•Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.
For UAT
(
Y
)
-K
(
A
)
,FD-K
For SkyAir, FD
(
Y
)
M-FA, FDY-KA,
FDYB-KA, FVY(P)J-A, FXUQ-MA
Central control adaptor kit
DTA112BA51
For SkyAir FFQ-B, FHQ-BV,
FAQ100BV, FBQ-B
Notes: 1. Installation box for adaptor must be obtained locally.
2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary.
3. For residential use only. Cannot be used with other centralised control equipment.
•Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
(128 units). Can turn units ON/OFF twice per day.
Note 2
DST301BA61
Schedule timer4