Daikin MERCA User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
))
^d]pa lqh] mfal
Quick fixing system for wall/ceiling mounting
Straight duct connector is mounted
to discharge side
Standard air filter : removable from the bottom
FWD04-18A*
2-pipe (*=T) 4-pipe (*F)
04 06 08 10 012 016 018 04 06 08 10 012 016 018
Power input W 234 349 443 714 1197 234 349 443 714 1197
Capacity
Cooling capacity
Total capacity kW 3.90 6.20 7.80 8.82 11.90 16.40 18.30 3.90 6.20 7.80 8.82 11.90 16.40 18.30
Sensible capacity kW 3.08 4.65 6.52 7.16 9.36 12.80 14.10 3.08 4.65 6.52 7.16 9.36 12.80 14.10
Heating capacity (2-pipe) kW 4.49 6.62 9.21 15.86 21.15 -
Heating capacity (4-pipe) kW - 4.05 7.71 9.43 10.79 14.45 19.81 21.92
Dimensions HxW x D
280
x754
x559
280
x964
x559
280
x1174
x559
280
x1174
x559
352
x1384
x718
280
x754x
559
280
x964
x559
280
x1174
x559
352
x1174
x718
352
x1384
x718
mm
Machine weight kg 35 43 50 52 71 83 86 33 41 47 49 65 77 80
Sound level Sound power dBA 66 69 72 74 78 66 69 72 74 78
Water pressure drop
Cooling kPa 17 24 16 26 34 45 17 24 16 26 34 45
Heating kPa 9 15 13 12 16 14 20 13 21 28 37
Fan
Air flow rate m³/h 800 1250 1600 2200 3000 800 1250 1600 2200 3000
Available pressure Pa 63 53 63 59 92 138 128 66 58 68 64 97 145 134
Water connections Std. heat exchanger inch 3/4 1 3/4 1
Required power supply V/ f / Hz 230/1/50
Water flow
Cooling l/h 674 1,064 1,339 1,514 2,056 2,833 3,140 674 1,064 1,339 1,514 2,056 2,833 3,140
Heating l/h 674 1,064 1,339 1,514 2,056 2,833 3,140 349 581 808 1,392 1,856
* : T(2-pipe) - F(4-pipe)
> O <
>O<(,9
=;>O=J.
>O<(,9
EPC_08-406.indd 11 26-03-2008 16:14:53