INSTALLATION MANUALSystem air conditionerEnglishFrançaisEspañolRXYQ72PAYDRXYQ96PAYDRXYQ108PAYDRXYQ144PAYDRXYQ168PAYDRXYQ192PAYDRXYQ72PATJRXYQ96PATJRXY
5 English6. REFRIGERANT PIPINGNOTE• All field piping must be installed by a licensed refrigeration technician and must comply with relevant local and
English 613. High side equalizer accessory pipe (1)14. L type accessory joint (1)15. L type accessory joint (2)16. Liquid side accessory pipe (2)17. L
7 English(4) If the piping length between the outside units exceeds 80 in., cre-ate a rise of 8 in. or more in the gas piping under a length of 80 in.
English 86-5 Example of connectionExample of connection(Connection of 8 indoor units)(*1) “ ” Indicate the Outside unit multi
9 EnglishOutside unit multi connection piping kit andRefrigerant branch kit selectionPipe size selection• Refrigerant branch kits can only be used wit
English 10Required Conditions Example Drawings1. It is necessay to increase the pipe size between the first branch kit and the final branch kit. (Redu
11 English7. FIELD WIRINGNOTE• All field wiring and components must be installed by a licensed elec-trician and must comply with relevant local and na
English 12NOTE• Open the knock holes with a hammer or the like.• After knocking out the holes, we recommend you remove any burrs and paint them using
13 English• When two wires are connected to a single terminal, connect them so that the rear sides of the crimp contacts face each other. Also, make s
English 14<Air tight test>Pressurize the liquid pipe, gas pipe, and equalizer pipe from the ser-vice ports of each shutoff valve to 550 psi (do
figure 1 figure 3figure 2figure 4figure 6figure 5figure 7 figure 8figure 9figure 10 figure 11 figure 12-121≥3/8≥3/8≥3/8≥3/4≥3/4≥2≥2≥2≥7-7/8≥15-3/4 ≥15
15 EnglishTightening torqueThe sizes of the shutoff valves on each model and the tightening torque for each size are listed in the table below.<Siz
English 16• Use an insulated rod to operate the push buttons via the EL. COMPO. BOX’s inspection door.There is a risk of electric shock if you touch a
17 English[Automatic refirgerant charging operation procedure]NOTE• The marks of LED mean as follows.h : OFF i : ON j : Blinking ∗ : OFF, ON or Brinki
English 186.After completing the additional refrigerant charging, record the charging amount on the accessory “REQUEST FOR THE INDICATON” label (Insta
19 English13-3 Checks After Test RunPerform the following checks after the test run is complete.• Record the contents of field setting.→ Record them o
1645 Wallace Drive, Suite 110Carrollton, TX [email protected] EM09A060A(1002)FS
figure 17figure 18-1figure 14figure 15figure 13figure 18-2figure 16figure 12-2figure 19123546111258961013777771111513-113-213-362344CD78A34152B1212345
figure 23figure 20figure 21figure 22figure 24figure 2512F1 F2 F1 F2F1 F2 F1 F2F1 F21(A1P)231234512348910411L1 L2 L312567123456789101211 12345678910131
figure 31figure 26figure 29 figure 30figure 32figure 27 figure 281212312345122356412341013115678912(): 15: 16: 17: 181412341112139141056789(): 15: 16:
1 EnglishRXYQ72PAYDRXYQ96PAYDRXYQ108PAYDRXYQ144PAYDRXYQ168PAYDRXYQ192PAYDRXYQ72PATJRXYQ96PATJRXYQ108PATJRXYQ144PATJRXYQ168PATJRXYQ192PATJVRVIII System
English 2• Make sure that all wiring is secured, that specified wires are used, and that no external forces act on the terminal connec-tions or wires.
3 English1-3 Disposal requirementsDismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance w
English 45.The space around the unit is adequate for servicing and the mini-mum space for air inlet and air outlet is available.(See the “Installation