INSTALLATION MANUALR410A Split SeriesModels RXS50E2V1B RKS50E2V1BRXS60E2V1B RKS60E2V1BRXS71E2V1B RKS71E2V1BRYN50E2V1B RYN60E2V1BRN50E2V1B RN60E2V1BARX
English 8Pump Down OperationIn order to protect the environment, be sure to pump down when relocating or disposing of the unit.1) Remove the valve li
9 EnglishWiringWARNING1) Do not use tapped wires, stand wires, extensioncords, or starbust connections, as they may cause overheating, electrical sho
English 10CAUTIONWhen connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. Problems with the w
(0601) HT3P159684-2F M05B071A00_CV_3P159684-2F.fm Page 2 Wednesday, November 30, 2005 9:20 AM
Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome,Kita-ku, Osaka, 530-8323 Japan 2SB63475-5BRXS50E2V1B, RXS60E2V1B, RXS71E2V1B, RKS50E2V1B, RKS60E2V1B,
1 EnglishSafety Precautions• Read these Safety Precautions carefully to ensure correct installation.• This manual classifies the precautions into WAR
English 2AccessoriesAccessories supplied with the outdoor unit:Precautions for Selecting the Location1) Choose a place solid enough to bear the weigh
3 EnglishOutdoor Unit Installation DrawingsModelMax. allowable heightMin. allowable lengthMax. allowable length30m1.5m20m60 class50 class 71 classLiq
English 4Installation Guidelines• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation
5 EnglishOutdoor Unit Installation3.Flaring the Pipe End1) Cut the pipe end with a pipe cutter.2) Remove burrs with the cut surface facing down-ward
English 65.Purging Air and Checking Gas Leakage• When piping work is completed, it is necessary to purge the air and check for gas leakage.WARNING1)
7 EnglishOutdoor Unit Installation6.Refilling The RefrigerantCheck the type of refrigerant to be used on the machine nameplate.Precautions when addin